Magic-Pak HWC8-12 Скачать руководство пользователя страница 2

Page 2 of 18

507388-01

Issue 1504

clearances to combustible material held to 0” sides, 2” top, and 

1” front and plenum.  Adequate clearance must be provided to 

install the union and manual shutoff valve as well as providing 

accessibility for field wiring.  Do not install directly on carpeting, 

tile, or other combustible material other than wood flooring.

The grille side of the unit may be flush with, or extend beyond, the 

face of the exterior wall, but should not be recessed more than 

2” from the face of the building and should not be obstructed 

with trees, landscape materials, or building structure.

There is no minimum clearance required on locating the unit to 

an interior corner of a building.

If the unit is to be enclosed, provisions should be made allowing 

access to the indoor side of the unit for changing filters and for 

inspection.  At least 29” of unobstructed space should be provided 

in front of the indoor side, whether enclosed or not, to permit 

removal of the cooling chassis should repairs or inspection be 

required.

If the unit is installed in a residential garage, it must be located 

or protected to avoid physical damage by vehicles. Unit must be 

installed so the burners and ignition source are not less than 18” 

(457 mm) above the floor. This unit must be installed so that no 

electrical components are exposed to water.

This appliance should be installed in a location such that the vent 

outlet is located in the following manner:

1.  Distances to windows that open, building openings, or public 

walkways should be consistent with the National Fuel Gas 

Code Z223.1 or CAN/CGA-B149.1 & .2.

2.  For  U.S.  installations,  the  vent  system  shall  terminate  a 

minimum horizontal clearance of 4’ from electric meters, 

regulators, and relief equipment.  For installations in Canada, 

refer  to  the  current  CAN/CGA-B149.1  &  .2  or  with  the 

authorities having local jurisdiction.

3.  Flue  products  will  not  cause  degradation  to  building 

materials.

This furnace design is not listed for installation in mobile 

homes, recreational vehicles, or outdoors.

Use of Furnace as a Construction Heater

Allied Air does not recommended the use of these units as a 

construction heater during any phase of construction.  Very 

low return air temperature, harmful vapors and operation of 

the unit with clogged or misplaced filters will damage the unit.

Units may be used for heating of buildings or structures  

under construction, if the following conditions are met:

  The Unit must be permanently installed per these 

installation instructions.

  A room thermostat must control the furnace. The use 

of fixed jumpers that will provide continuous heating is 

not allowed.

INSTALLATION

General

These instructions must be hung on or near the furnace in a 

conspicuous place.

The HWC8 V-Series

 units are self-contained, gas-fired heating 

with electric cooling models.  The unit design has been certified by 

Intertek Testing Services for compliance with the latest edition of 

the American National Standard – ANSI Z21.47/National Standard 

of Canada – CAN/CGA-2.3 for direct vent central furnaces.  The 

HWC8 models are certified to be in compliance with the latest 

edition of A.H.R.I. Standard 390.   All models are design certified 

for heating operation when fired with natural or propane gas.

These installation instructions are intended as a general guide 

only, for use by an experienced, qualified contractor.

Inspection

The unit is shipped in one package, completely assembled and 

wired.  The Evaporator drain tubing is in the cooling compartment 

behind the filter access panel.

If any damage is found, proper notation should be made on the 

carrier’s freight bill.  Damage claims should be filed with the 

carrier as quickly as possible.

Check the rating plate to confirm heating and cooling capacities.  

The unit should be operated only with the type of gas and 

electrical supply noted on the rating plate.

IMPORTANT:  Remove the chassis hold down shipping bracket 

before installation.  These brackets are located on the outdoor 

side of the unit below the louver panels.

Location

The design is certified for indoor installation only. The interior 

portions of the unit may be surrounded by a closet with 

In the State of Massachusetts:

This product must be installed by a licensed Plumber or Gas 

Fitter.  When flexible connectors are used, the maximum 

length shall not exceed 36”.  When lever-type gas shutoffs 

are used, they shall be T-handle type.

 

 WARNING

Install operate and maintain unit in accordance with 

manufacturer’s  instructions.  The  State  of  California  has 

determined that this product may contain or produce  

chemicals, in very low doses, which may cause serious 

illness or death. it may also cause cancer, birth defects or 

reproductive harm.

 

 WARNING

Содержание HWC8-12

Страница 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Installati...

Страница 2: ...ion of the unit with clogged or misplaced filters will damage the unit Units may be used for heating of buildings or structures under construction if the following conditions are met The Unit must be...

Страница 3: ...d upon construction completion The input rate and temperature rise must be set per the furnace rating plate One hundred percent 100 outdoor air must be provided for combustion air requirements during...

Страница 4: ...ing compound The seal must be weathertight to prevent entrance of moisture and water into the building Assure that the unit is completely seated against the gaskets on the wall sleeve Installing Witho...

Страница 5: ...ustion inducer The inducer draws the combustion products out of the heat exchanger together with dilution air and forces the mixture from the unit to the outside No special provisions are required for...

Страница 6: ...manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pressures in excess of 1...

Страница 7: ...all sides of the duct are flanged over to permit removal of the cooling chassis if required Use a flexible connection to attach the remainder of the return duct The return duct should be sealed to th...

Страница 8: ...55 770 58 735 61 700 64 208 860 52 815 55 770 58 735 61 230 880 51 835 54 790 57 750 60 TAP 1 HEAT 208 or 230 735 49 700 51 670 53 640 56 TAP 2 HEAT 208 or 230 825 43 795 45 770 46 745 48 TAP 3 HEAT 2...

Страница 9: ...me additional installation and operating precautions should be taken The following precautions are taken to prevent possible vent system ice blockage that could result in safety shutdown of the burner...

Страница 10: ...after the thermostat is satisfied The time delay is preset at the factory and timing can not be adjusted Cooling Sequence of operation When the thermostat system switch is set for COOL the blower wil...

Страница 11: ...osen these screws to remove control board mounting bracket Ignition Control board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Страница 12: ...wires at the gas valve 7 Refer to Figure 6 Remove the two screws on the burner assembly that secure it to the mounting brackets The mounting brackets contain pins to locate the assembly and hold it in...

Страница 13: ...Page 13 of 18 507388 01 Issue 1504 BURNER MANIFOLD ASSEMBLY REMOVAL Step 7 Mounting Brackets Step 8 Step 9 Step 10 Burner Manifold Assembly Figure 6...

Страница 14: ...nd slip the rollout switch from beneath the lanced tab on the burner assembly 4 For reassembly follow the above steps in reverse order Flame sensor 1 Remove the control board mounting bracket as descr...

Страница 15: ...frigeration system contained in the cooling chassis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited...

Страница 16: ...Page 16 of 18 507388 01 Issue 1504 Figure 7...

Страница 17: ...Page 17 of 18 507388 01 Issue 1504 Figure 8...

Страница 18: ...Page 18 of 18 507388 01 Issue 1504 NOTES...

Отзывы: