Input Power

R2-24…….24Vac 

R2-120….120Vac 

R2-220….220Vac 

Output Contacts (1,3 or 1,4 ) 

10 Amps @ 120vac 

5 Amps @ 220vac 

10Amps @ 30vdc 

R2 Controller

Installation Instructions 

Conductivity Sensor Configuration

Input power is connected between pins 2 and 7

Wire the “Common Probe” to pin 5

Wire the “Lower Probe” to pin 6

Wire the “Upper Probe” to pin 8

Pins 1-3 and 1-4 are isolated switched contacts  

to switch power to a valve or pump 

© Copyright Madison Company – ECR #5936, Effective Date 10/2011; MF-044, Rev F

Madison Company  •  (203) 488-4477  •  (800) 466-5383  •  Fax (203) 481-5036  •  [email protected]  •  www.madisonco.com

 

ISO 9001 Certified

Conductivity Sensor Configuration

• 

Input power is connected between pins 2 and 7

• 

Wire the “Common Probe” to pin 5

• 

Wire the “Lower Probe” to pin 6

• 

Wire the “Upper Probe” to pin 8

Pins 1-3 and 1-4 are isolated switched contacts to switch power to a valve or pump

© 2018 Madison Company, Inc., MAD_MAN_MF-044_060518

ECR #10900, Effective Date 8/2018, MF-044, Rev G