U5098 Series Ultrasonic Sensors Manual
099-MF179 - Installation
Page. 10 of 40
www.madisonco.com
U5098 -
installation
Agitators presence
Level measurement when using agitators in the tank is possible due to the auto-tuned statistical filter. Adjustment of
the filter settings is rarely needed, but if required, the U5098 sensor programming parameters may be edited as
follows in the MODBUS RTU Software:
FILTER; this parameter is available in the “ User Setup” screen; increasing the parameter value decreases the
sensor sensitivity to the level measurement sudden variations.
F-WINDOW; this parameter is available in the “ User Setup” screen; decreasing the parameter programmed value
increases the sensor immunity to false echoes.