Figure 3-10 – Relay Statues Screen
•
Failsafe
controls relay activation for the common relays.
Failsafe ON
causes these relays to de-energize
during alarm conditions and energize when there is no alarm. With
Failsafe
active, a power failure forces
the relay contact to the alarm position.
•
Horn
controls how activating this relay will affect the horn driver circuit connected to J2 on the
motherboard. Choices are
NO
,
STEADY
or
PULSE
. Warning level alarms might be set to pulse the horn with
high alarms set for steady. Personnel then know which alarm level is present by hearing the pulsing or
steady horn.
•
Turning
Acknowledge
ON
(not allowed on Relay 1) allows Relay 2 to be deactivated during alarm conditions
by an Alarm Reset. This is useful if another audible device is being driven by the relay. The acknowledge
feature is not available for Relay 1 since it is often used for driving a warning light and Relay 2 for driving a
horn. It could be dangerous if an operator acknowledged the horn AND the light since no indication of the
high alarm condition remains.
3.4.2
Horn / Piezo Menu
•
The TXP-C20 display PCB is equipped with a small audible piezo that chirps when keys are pressed providing
an audible feedback to the operator. It also may be set to audibly indicate alarm conditions by entering YES
into the
Piezo On
menu item in Figure 3-11. This piezo will then mimic the
Horn
settings menus described in
section 3.3.1.
•
The
Horn ACK
menu item determines if the Horn Driver output may be acknowledged by an Alarm Reset.
YES
causes an Alarm Reset to silence the horn even though an alarm condition remains active.