Macurco RD-24 Скачать руководство пользователя страница 17

 
Macurco

TM

 Macurco RD-24 Manual 

 

 

REV 

 1.0.0 

[34-8708-4770-1] 

17 

|

 

P a g e

 

 

6.1

 

Read Configuration 

Device configuration is indicated by 2 bytes. 

bit 

15 

bit 

14 

bit 

13 

bit 

12 

bit 

11 

bit 

10 

bit9  bit8 

bit 

bit6  bit5  bit4 

bit 

bit2  bit1  bit0 

Module # 4 

Module #3 

Module #2 

Module #1 

0000 = relays  

0000 = relays  

0000 = relays  

0000 = relays  

0001 = analog outputs 

0001 = analog outputs  0001 = analog outputs 

0001 = analog outputs 

0010 = analog inputs 

0010 = analog inputs 

0010 = analog inputs 

0010 = analog inputs 

0011 to 1110 - future 

0011 to 1110 - future 

0011 to 1110 - future 

0011 to 1110 - future 

1111 = No exp. board 

1111 = No exp. board 

1111 = No exp. board 

1111 = No exp. board 

 

6.2

 

Fail-safe 

Device fail safe configuration uses 4 bytes. 

bit15  bit14  bit13  bit12  bit11  bit10  bit9  bit8  bit7  bit6  bit5  bit4 

bit3 

bit2 

bit1  bit0 

Fail safe timer value  30 to 3600  (seconds) 

state 

0=OFF 

1=ON 

Active 
0=NO 
1=YES 

 

bit15  bit14  bit13  bit12  bit11  bit10  bit9  bit8  bit7  bit6  bit5  bit4 

bit3 

bit2 

bit1  bit0 

Analog Output value when in fail safe condition: (mA x 100) 

0 = 0mA 

2000 = 20.00mA 

 
6.3

 

Configure Analog Outputs Range 

Expansion Board #4 

Expansion Board #3 

Expansion Board #2 

Expansion Board #1 

bit15  bit14  bit13  bit12  bit11  bit10  bit9  bit8 

bit7 

bit6  bit5  bit4  bit3 

bit2  bit1  bit0 

DAC2 

DAC1 

DAC2 

DAC1 

DAC2 

DAC1 

DAC2 

DAC1 

rng 

rng 

rng 

rng 

rng 

rng 

rng 

rng 

rng

: ‘0’ –

 

4 to 20 mA (2 to 10V), ‘1’ 0 to 20mA (0 to 10V) 

 

 

6.4

 

Multipurpose command 

Multipurpose command uses 2 bytes, and can be used on the following situations: 

 

Control all relays of a remote driver (RD-24) device. 

 

Control all analog outputs of remote drivers with same value. 

 

Control remote drivers with analog outputs and relays with same output values for relays and same output 
values for analog outputs. 

 

Command to prevent a failsafe timeout when there is no change in the state of the outputs. 

Содержание RD-24

Страница 1: ...IMPORTANT Keep these user instructions for reference Macurco RD 24 Modbus Remote Driver Installation Operation Manual...

Страница 2: ...ion Connection 6 3 2 4 Input Output Connections 7 3 2 5 Expansion Board Connections 8 4 Operations 9 4 1 Power up 9 4 2 Initial Operating Mode 9 4 2 1 RD 24 Settings 9 4 2 2 Programming Mode 9 4 2 3 C...

Страница 3: ...analog outputs or analog inputs Using Modbus communication you can control multiple I O based on the application The RD 24 requires 24VDC to operate and can be used to engage or disengage other equipm...

Страница 4: ...mmunication Slots 1 4 Baud Rate 4800 9600 19200 default 98400 57600 115200 bps Enclosure NEMA 4X Warranty Two year limited warranty 3 Installation Instructions 3 1 Location Mounting Macurco RD 24 is s...

Страница 5: ...button of the connector use flat headed screwdriver insert bare wire into respective wire cavity of the connector and release the white button Ensure that the wire cannot be easily pulled from the co...

Страница 6: ...e twisted pair providing a pair for signal A B common COM and shield ground SHD connection NOTE Running the RS 485 cable adjacent to or in the same conduit with high voltage wires is not recommended a...

Страница 7: ...7 P a g e 3 2 4 Input Output Connections Figure 3 4 RD 24 Board Diagram Macurco RD 24 Dip Switch EOL Resistor RS 485 COMMS IN OUT POWER IN OUT Expansion Board 2 SHD COM B A SHD COM B A GND GND 24V 24...

Страница 8: ...ted 55mA Figure 3 5 Relay Expansion Board 3 2 5 2 Expansion Analog Output Board Expansion Analog Input Board 2 Analog Outputs Both outputs at 4mA Current 32mA Both at 20mA Current 70mA Figure 3 6 Anal...

Страница 9: ...D 24 4 2 2 Programming Mode When the RD 24 is powered with address set to 254 it enters programming mode The STATUS LED will be flashing RED and GREEN alternatively every 200 milliseconds to indicate...

Страница 10: ...the dip switch address to 255 and power on the RD 24 for at least 3 seconds The LED below the dip switch should blink green rapidly After at least 3 seconds power off the RD 24 Using the dip switch ch...

Страница 11: ...lect DELETE RELAY from the RELAYS menu and press ENTER Input the relay number to delete and press ENTER to delete all relays assigned to the zone input 0 and press ENTER The relay s will be deleted fr...

Страница 12: ...I O Chart at the end of this manual To assign 4 20mA output to a zone select 4 20MA OUTPUT from the zone configuration menu and press ENTER Then select OUTPUT NUMBER and press ENTER Figure 4 4 Zone 4...

Страница 13: ...and NO2 sensor reading is 10 0ppm which corresponds to 12mA then the 4 20mA or Analog output assigned to the zone will output 12mA SCALE In this mode the 4 20mA value for all detectors added to a zon...

Страница 14: ...that can be connected to the controller The sensor mapping will be done from top to bottom It grows from sensor 192 all the way to 128 By default DVP 1200 allocates space to connect to 192 digital se...

Страница 15: ...ement 6 Figure 3 4 RD 24 Board Diagram 7 Figure 3 5 Relay Expansion Board 8 Figure 3 6 Analog Output Expansion Board 8 Figure 3 7 Analog Input Expansion Board 8 Table 4 1 Baud Rate Configuration 9 Tab...

Страница 16: ...00 00 00 00 00 00 00 00 00 85 4D 0x03 2 2 8 Vendor url Returns vendor url in C 01 03 00 15 00 08 55 ASCII C8 www macurco com R 01 03 10 77 77 77 2E 6D 61 63 75 72 63 6F 2E 63 6F 6D 00 A2 D6 0x03 3 0...

Страница 17: ...to 3600 seconds state 0 OFF 1 ON Active 0 NO 1 YES x x bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0 Analog Output value when in fail safe condition mA x 100 0...

Страница 18: ...elays or two Analog outputs Bit12 defines which output to be controlled 0 output1 1 output 2 bit11 Defines the state of relays 0 OFF and 1 ON bit10 Value to be written to the analog output DAC 0 2000...

Страница 19: ...Number _______________________________ Location of Install _________________________ Installed by _________________________________ Remote Device I O Chart Relay connection Connected device Zone Conf...

Страница 20: ...4 20mA output 13 4 20mA output 14 4 20mA output 15 4 20mA output 16 4 20mA output 17 4 20mA output 18 4 20mA output 19 4 20mA output 20 4 20mA output 21 4 20mA output 22 4 20mA output 23 4 20mA outpu...

Страница 21: ...5 1 191 4 20mA input 16 1 192 4 20mA input 17 2 161 4 20mA input 18 2 162 4 20mA input 19 2 163 4 20mA input 20 2 164 4 20mA input 21 2 165 4 20mA input 22 2 166 4 20mA input 23 2 167 4 20mA input 24...

Страница 22: ...47 3 159 4 20mA input 48 3 160 4 20mA input 49 4 129 4 20mA input 50 4 130 4 20mA input 51 4 131 4 20mA input 52 4 132 4 20mA input 53 4 133 4 20mA input 54 4 134 4 20mA input 55 4 135 4 20mA input 5...

Страница 23: ...ES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO 2 YEARS FROM THE PURCHASE DATE Macurco shall not be liable for any incidental or consequential damages for breac...

Отзывы: