Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
61
|
P a g e
7
Testing & Maintenance
Macurco recommends performing the DVP Functionality Test at least once a year.
7.1
Testing
7.1.1
Keypad Test
1.
Power down the DVP-120C.
2.
Remove the Jumper Shorting Connector from the EXT header and place the Jumper Shorting Connector
onto the top two pins of the SYS header.
3.
Power up the DVP-120C and close the panel door. The LCD will display “Current Password ####” for 3
seconds (where #### is the current set password) then will display “V24 =##. #-OK”, where V24 is the
expected Power Supply output voltage and the ##.# is the actual Power Supply output voltage. If the
status is OK, then proceed to the test process by pressing 0 key.
4.
Read and follow the instruction on the LCD to test the keypad. When finished, the LCD will display
“Keypad Test OK 0-Control Buzzer”.
5.
Press 0 key to test the buzzer. You will hear the buzzer sound. To turn off the sound, press the 0 key
again.
6.
When the keypad test has passed, and the buzzer sound is good, turn off the power of the DVP-120C.
7.
Remove the jumper shorting connector from SYS header and install onto the two bottom pins of EXT
header 24V.
8.
Turn ON the DVP-120C and it should operate as explained in section
7.1.2
Functionality Test
1.
Turn off the DVP-120 or DVP-120C.
2.
For DVP-120 move the jumper from bottom two pins of EXT connector to pins 1 and 2 of EXT connector.
For DVP-120C, move the jumper in J10 to left two pins of J10.
3.
Turn on the DVP-120 or DVP-120C.
Self-test is performed when the panel is powered on with a jumper in the position indicated in above step. A self-
test pass is indicated by “Test Mode mm: ss – Press any key” on the LCD where “mm” are minutes and “ss” are
seconds. Confirm “ss” is incremented every second.
4.
Press following keys in the keypad to test corresponding functionality.
Key in Keypad
Functionality Test
0
Strobe
9
Horn
Menu
Relay 1
Hush
Relay 2
Up
Relay 3
Right
Buzzer
Table 7-1 Keypad keys for Testing Functionality
5.
If all test is complete, turn off the DVP-120 or DVP-120C. Move the jumper back to bottom two pins of
EXT connector for DVP-120 and right two pins of J10 for DVP-120C.
Содержание DVP-120C
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...