Macurco CX-xx Manual (Rev-1.0) Eng
REV – 1.0
[34-2900-0512-0 ]
28
|
P a g e
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
13 times to get to “420” or 4-20mA Output Setting.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.5.16
Select 4-20mA Mode – “420.n”
Available options are “dUAL” (default), “HigH”.
NOTE
: Dual Mode must be used when the detector is connected to a Macurco DVP control panel. High Mode should
only be used when the detector is used as a standalone unit.
To select the 4-20mA Mode, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
14 times to get to “420.n” or 4-20mA Mode.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
4.5.17
Select Calibration Period for CO Sensor – “CAL.C”
The value selected for Calibration Period is the number of months. The CX-xx indicates a “calibration due” when it is
within 1 month of the calibration period, and a “calibration overdue” when the detector has reached or exceeded
the calibration period. The Calibration Period setting cannot be changed if the CX-xx is indicating “calibration due” or
“calibration overdue”.
Available options are “diS” (default), 3, 6, 12, 24.
To select the Calibration Period for the CO sensor, in normal mode:
1.
Push the
Next
button to get to “Con” or the Configuration menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push
Next
15 times to get to “CAL.C”.
4.
Push
Enter
. The display will show the current setting.
5.
Push
Next
to cycle through the available settings (display will begin flashing).
6.
Push
Enter
to confirm the new setting (display will stop flashing).
7.
Push
Enter
once more to return to the configuration menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to return to normal operation.
Содержание CX-6
Страница 42: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 42 P a g e 9 Appendix B Menu Structure 9 1 Main Menu...
Страница 43: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 43 P a g e 9 2 Auto Test Menu bUZ...
Страница 44: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 44 P a g e 9 3 Configuration Menu CON...
Страница 45: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 45 P a g e...
Страница 46: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 46 P a g e...
Страница 47: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 47 P a g e...
Страница 48: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 48 P a g e...
Страница 49: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 49 P a g e...
Страница 50: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 50 P a g e...
Страница 51: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 51 P a g e 9 4 Select Test Menu tst...
Страница 52: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 52 P a g e 9 5 CAL Menu...
Страница 53: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 53 P a g e...
Страница 54: ...Macurco CX xx Manual Rev 1 0 Eng REV 1 0 34 2900 0512 0 54 P a g e 9 6 SEn Menu...