Seven years after the CM-E1 is installed the end-of-life signal will be activated indicating that the CM-E1 has reached the 
end of its service life and needs to be replaced. The end-of-life signal will cause an open circuit in the normally closed 
(NC) Trouble Relay to provide actuation of the signal circuits. The status LED will flash alternate AMBER and OFF every 
2 seconds and the CM-E1 buzzer will emit a short "chirp" every 50 seconds. The end-of-life buzzer can be silenced for 48 
hours by pressing the "TEST/RESET" button. The silencing of the buzzer also resets the Trouble Relay to the Normally 
Closed (NC) position. The silence function will continue to be available for 29 days after the CM-E1 initiates an end-of-life 
signal. After this 29 day period the CM-E1 can no longer be silenced and must be replaced. 

ERRORS 

The CM-E1 continuously monitors various internal operating parameters. If a problem is found, the unit will switch to 
Trouble mode. See TROUBLE INDICATOR section. To reset the unit for normal operation, press the TEST/RESET 
switch, or remove power to the unit, wait a few seconds, then re-apply unit power. If this problem persists, your detector 
requires repair; contact the alarm panel installer or Macurco Tech Support for advice. If repair is required, return the unit 
to manufacturer to comply with warranty. 

MAINTENANCE 

Do not disassemble unit or attempt to repair or modify any component of this detector.  This detector contains no user serviceable 

parts, and substitution of components may adversely affect product performance and result in sickness or death. 

 

The CM-E1 has a highly linear electrochemical sensor. The CM-E1 has an expiry function associated with the 
installation date which will cause the unit to indicate “

end-of-life”

 when the sensor has expired. 

See section "End-

of-life Indicator" 

All maintenance and repair of products manufactured by Macurco are to be performed at the 

Macurco Service Center. Macurco does not sanction any third-party repair facilities. 
TESTING 
The CM-E1 should be tested monthly by pushing the TEST/RESET switch; see TEST/RESET switch section. 

Normally this will be the only test required for the CM-E1 and is the recommended way to test the unit or units 
after installation. All CM-E1 units are factory calibrated and 100% tested for proper operation. The unit also has 

the ability to automatically self test and does so every 2 1/2 minute cycle. If the unit detects an improper voltage 
or inoperable component it will default into Trouble mode. 

See TROUBLE INDICATOR section. 

Check that the 

CM-E1 status indicator light is illuminated, (GREEN) continuously. If not, do not proceed with the tests. Though 
there is no field calibration procedure for this unit, there is an optional field test procedure.  
CLEANING 

The CM-E1 should be cleaned using the soft brush attachment of your vacuum cleaner. The CM-E1 should be tested 
after cleaning to ensure the unit is operating normally.  

SENSOR POISONS 
The gas sensor in the detector is designed with extreme sensitivity to the environment. As a result, the CO 

sensor may be damaged if it is exposed to a direct spray from aerosols such as paints, silicone vapors, etc., or 
to a high density of corrosive gases such as hydrogen sulfide or sulfur dioxide for an extended period of time. 

The sensor may react to chemicals such as ammoniated cleaning agents, volatile solvents and hydrogen gas. 
In sufficient concentration, these chemicals may cause a false alarm. 

CAUTION: This detector will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present 

in other areas. Accommodation spaces should be well ventilated when household cleaning supplies or similar contaminants are used. 

(UL 2034) 

 

 
 

!    WARNING 

!    WARNING 

Содержание CM-E1

Страница 1: ...lling or using this equipment must read and understand the information in these User Instructions before use Installation of this equipment by untrained or unqualified persons or use that is not in ac...

Страница 2: ...4 Do Not Use For 4 General Description 5 Features 5 Specifications 5 INSTALLATION AND OPERATION INSTRUCTIONS 5 Location 6 Installation 6 Power Up 7 Operation 8 Alarms 8 Reset Silence Switch 9 Trouble...

Страница 3: ...ing which means that higher levels of the gas being monitored may be present and could result in overexposure and cause sickness or death For proper use see supervisor or User Instructions or call Mac...

Страница 4: ...rstand the information in these User Instructions before use Installation of this equipment by untrained or unqualified persons or use that is not in accordance with these User Instructions may advers...

Страница 5: ...er Move to fresh air hazardous condition is present Highly linear electrochemical sensor N O or N C SPST Alarm Relay and N C SPST Trouble relay to connect to Alarm Control Panels Buzzer Produces repea...

Страница 6: ...te component 3 The detector may be installed on either a ceiling or a wall If installed on a peaked gabled or sloped ceiling it should be located about 3 feet 1 meter from the highest point The unit c...

Страница 7: ...and visual alarms If the self test fails or all the alarms do not activate do not use Failure to do so may adversely affect product performance and result in sickness or death When the detector is fi...

Страница 8: ...ONS ARE ACCOUNTED FOR DO NOT RE ENTER PREMISES NOR MOVE AWAY FROM THE OPEN DOOR WINDOW UNTIL THE EMERGENCY SERVICES RESPONDERS HAVE ARRIVED THE PREMISES HAS BEEN AIRED OUT AND THE ALARM REMAINS IN ITS...

Страница 9: ...will cause the buzzer to sound for two complete alarm cycles and status light to turn red for 5 seconds and then switch to solid amber The alarm relay will then be activated and the switch can be rel...

Страница 10: ...the sensor has expired See section End of life Indicator All maintenance and repair of products manufactured by Macurco are to be performed at the Macurco Service Center Macurco does not sanction any...

Страница 11: ...ss warranties obligations or liabilities THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO 2 YEARS Macurco shall not be liable for any inciden...

Отзывы: