■ Wiring Precautions
Be sure the wiring is done correctly by checking the product’s rated voltage and the terminal layout. Incorrect
wiring could result in fire, damage or malfunctions.
Tighten the terminal screw with the specified torque. If the screws of terminal are loose, it could result in
short circuit, fire, malfunctions.
FG Terminal must be used a dedicated ground. Not doing so could result in malfunctions.
a. Grounding should be the Class 3 grounding. The cable for grounding should be more than 2㎟.
b. grounding point be closed to the products and make short the distance to the ground cable if possible.
Please see below.
■ Installation Precaution
Do not install the location which exceeds allowed temperature. Product can be damaged or shorten the life.
Especially Install environment as below should be avoided.
Do not Install product to the place which the ambient temperature is out of limits, from -10℃ to 50℃ or on
the surface of control board which high pressure equipment is installed.
Do not install to the place where strong shock or vibration continuously have impacted on product.
For indoor use only.
Use the product under 2000M altitude.
The length of the power cable must be no more than 3 m (10 feet).
■ Disposal Precaution
When you dispose of product and battery, please treat it as industrial waste. It can create poisonous substances
or explosion.
■ Battery Specification
Mounted on mainboard Model CTL920F Battery is not replaced by the user. If the battery has run out of service,
please contact our Customer Support Center for replacement and inspection.
Item
Content
Battery Voltage
DC 2.3V , 7.7mAh
Battery Model
CTL920F (lithium Rechargeable / non-exchangeable )
Battery Lifetime
Permanent (In case of ambient temperature 25℃)
*
The specifications are subject to change depending on the model
.
■ All field-wiring connections to this unit shall be from Limited Voltage / Limited Current, below 20~28 Vdc
isolated secondary source with an output fuse, or Class 2 secondary circuits.