background image

GENERAL

1.  This document provides detailed information on how to install and operate the BPT Series of Surge Protection Devices (SPD)

2.  Locate a position to mount the SPD that will minimize the length of connecting wires required.  SPD’s should be 

located as close as possible to the AC panel or service area.  Mount the units using the mounting holes provided on the 

enclosure as shown by the illustrations in these instructions.  It is recommended that conduit, preferably metallic, be 

utilized to accomplish this connection.
3.  The BPT Series is installed and connected in parallel (“shunt”) across the AC supply to be protected. Connecting wires 

do not carry the supply current, only the short duration currents associated with the suppression of a transient event.

4.  Identified or indicated leads/wires must be connected exactly with respect to the AC Power feeding the SPD.  Failure 

to do so may result in damage to the device or post a danger to personnel.  

5.  Installation of this device should only be performed by a qualified licensed installer.  Incorrect installation may 

siginificantly impair the performance of the Surge Protection Device.  It is particularly important that all installation 

procedures and guidelines be followed exactly.
6.  Before starting any installation procedures, verify service voltages with an AC voltmeter to ensure that the correct SPD 

model has been selected.  

7.  Check to ensure that all connections are correct and secure before energizing.

8.  Keep this manual in a safe, dry place for future reference.

INSTALLATION INSTRUCTION

Before starting the installation, measure the Line voltage with an AC voltmeter to ensure the correct device has been 

selected for the current application.  The MCOV (maximum continuous operating voltage) CANNOT exceed the 

maximum limits for the following service voltages:

120VAC = 150MCOV

220VAC = 320MCOV

230VAC = 320MCOV

240VAC = 320MCOV

277VAC = 320MCOV

480VAC = 550MCOV

STANDARD ELECTRICAL CONFIGURATIONS

120 or 240VAC, Single Phase, 2 Wire + Ground

120 or 240VAC

PHASE

NEUTRAL

GND

PHASE A

NEUTRAL

GND

PHASE B

PHASE A

GND

PHASE B

PHASE C

NEUTRAL

PHASE A

GND

PHASE B

PHASE C

NEUTRAL

PHASE A

GND

PHASE B

PHASE C

120 /240VAC, Split Phase, 3 Wire + Ground

240 or 480VAC, Three Phase Delta, 3 Wire + Ground

120/240VAC, Three Phase Delta, 4 Wire + Ground

120/208VAC, Three Phase Wye, 4 Wire + Ground

or

277/480VAC, Three Phase Wye, 4 Wire + Ground

Requires a 1 Pole Breaker

[Figure #3]

Requires a 2 Pole Breaker

[Figure #4]

Requires a 3 Pole Breaker

[Figure #5]

Requires a 3 Pole Breaker

[Figure #6]

Requires a 3 Pole Breaker

[Figure #7]

120VAC

120VAC

240 OR 480

VAC

240 OR 480

VAC

240 OR 480

VAC

208 or 480

VAC

208 or 480VAC

208 or 480

VAC

240

VAC

240

VAC

208

VAC

120VAC

120VAC

(High Leg) “Orange”

120 or 277

VAC

120 or 277

VAC

120 or 277

VAC

NOTE:

Wye Configuration is 

also applicable for:

220/380VAC

230/400VAC

240/415VAC

1.  Connect the ground wire to the service panel ground buss.

2.  Connect the neutral wire from the service panel neutral buss to the lug labeled neutral. (Not Applicable for Delta Applications)

3.  Connect the phase (hot) wires from a 3 pole breaker to the SPD device connectors labeled phase “A”, “B”, and “C”, as appropriate.

4.  Attach and crimp (supplied) lug connectors to each #8 or #10 AWG wire, as required, before inserting it into the terminal block. 

5.  Tighten the lug screw securely.

6.  Check all connections to ensure they are correct and properly secured. 

G

PHASE

FAULT

N-G

FAULT

TEST

DISABLE

ENABLE

PHASE PHASE

NOTE: BEFORE 

ENERGIZING THE SPD: 

ENSURE ALL 

CONNECTIONS ARE 

CORRECT.  DO NOT  

ENERGIZE WITH FRONT 

COVER OPEN

3 POLE BREAKER

KEEP WIRES AS 

SHORT AS POSSIBLE

[Figure #8: 3 Ø Phase 

Wye Wire Hook-up]

[Figure #9: 3 Ø Phase Wye 

Breaker Hook-up]

Notes:

1.  For Single Phase Models, Phase “A” and Phase “C”

     lines are left vacant.

2.  For Split Phase Models, Phase “B” is left vacant.

3.  For Delta Configurations, the Neutral position is left

     vacant.

4.  Use #10 to 1/0 Wire for installation.

BPT (100/200) Models:

The specific product you have in service may be configured 

for any one of the following kA ratings: (100=100kA/Phase) 

and (200=200kA/Phase)

120 or 240VAC, Single Phase

120/240VAC, Split Phase

240 or 480VAC, 3 Phase Delta

120/208VAC, 3 Phase Wye 

120/240VAC, 3 Phase Delta

 

(High Leg)

277/480VAC, 3 Phase Wye

220/380VAC, 3 Phase Wye

230/400VAC, 3 Phase Wye

240/415VAC, 3 Phase Wye

[Figure #10: Internal Layout]

The device shall be fed from a 30 Amp breaker, in accordance 

to the number of poles required. 

 

Single Phase   = 1 Pole Breaker

 

Split Phase      = 2 Pole Breaker

 

Three Phase    = 3 Pole Breaker

 

High Leg Delta = Phase “B” Orange

 

Delta Units have no Neutral

Because the SPD is installed in parallel or shunt with the load, 

VA rating is not limited.

= 1 Pole Breaker

= 2 Pole Breaker

= 3 Pole Breaker

= Phase “B” Orange

Отзывы: