OUTPUT LOGIC

H

L

Voltage pulse

or

RS-422 line
driver pulse

Output

Non-inverted

Non-inverted

Dry contact

Input

H

L

H

L

OFF

ON

H

L

Inverted

Inverted

H

L

OFF

ON

OFF

ON

OFF

ON

OFF

ON

Open collector

Voltage pulse

RS-422 line driver  pulse

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 14 with a multimeter.

3) Input:  

• Check that the frequency is within the range described 

below.

  Dry contact, 12 V / 24 V pulse: ≤ 100 kHz
  5 V pulse: ≤ 500 kHz
  3.3 V pulse, RS-422 line driver pulse: ≤ 1 MHz
   And also, check that it doesn’t exceed the maximum fre-

quency of output signal.

• When operating at frequencies close to the maximum fre-

quency, use pulse duty at approx. 50%. 

4) Output:  Check that the load voltage meets the specifica-

tions described in the table below.

OUTPUT SIGNAL

LOAD VOLTAGE

Open Collector

50 V DC ≤ 100 mA

Voltage Pulse

3.3 V

≥ 660 Ω

5 V

≥ 1 kΩ

12 V

≥ 2.4 kΩ

5) Open the front cover to check the input pulse status with 

monitor LEDs.

Phase A: Green, Phase B: Red, Input low: LED on
(LED on/off is not defined at input opened.)

 

FRONT VIEW

Input Monitor LED Phase B (Red)

Input Monitor LED Phase A (Green)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.