STATUS INDICATOR LED

Combinations of the three front LEDs (LD1, LD2, LD3) indicate the transmitter’s operating status by different blinking pat-
terns.
Examples are shown below.

LD1

LD2

LD3

A

LD1

LD2

LD3

G

LD1

LD2

LD3

R

NORMAL OPERATION (RUN) MODE

ERROR MODE

Parameter Error
Error occurred when reading parameters from the 
internal memory.

LD1

LD2

LD3

A

A

G

Overrange Input
The input is below -15% or above 115%.

LD1

LD2

LD3

R

G

G

G A

Burnout

PC Configuration RUN Mode
The transmitter is configured via PC and 
is in normal operating conditions.

AD Conversion Error
Internal AD conversion error.

*

1. LD1 may be one of the

LD1

LD2

LD3

A

G

Output Limit
The output is at the upper or the lower limit.

Amber LED

Green LED

Red LED

OFF

ON

Blink

A

G

R

*

1

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit using the PC Configurator 
Software (model: W2CFG).

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.