OUTPUT RANGING
The internal DIP switch setting is required to select output
types before setting a precise output range using PC Con-
figurator Software (model: W2CFG).
For detailed information on the PC configuration, refer to
the W2CFG users manual.
Table 1. DIP switch setting: Output 1 type
OUTPUT 1 TYPE
SW1-1
SW1-2
SW1-3
SW1-4
0 – 20 mA DC
OFF
OFF
ON
OFF
-10 – +10 V DC
OFF
ON
OFF
ON
-5 – +5 V DC
ON
OFF
OFF
ON
Table 2. DIP switch setting: Output 2 type
OUTPUT 2 TYPE
SW2-1
SW2-2
SW2-3
SW2-4
0 – 20 mA DC
OFF
OFF
ON
OFF
-10 – +10 V DC
OFF
ON
OFF
ON
-5 – +5 V DC
ON
OFF
OFF
ON
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
If the potentiometer wires are broken, the output goes
over 100% (below 0% with downscale) due to burnout
function. Confirm the status indicator LED pattern and
check leadwires in such a case.
5) Output: Check that the load resistance meets the de-
scribed specifications.
6) LED: Confirm that the LEDs indicate the normal operat-
ing mode.
STATUS INDICATOR LED
Combinations of the three front LEDs (LD1, LD2, LD3) indicate the transmitter’s operating status by different blinking pat-
terns.
Examples are shown below.
LD1
LD2
LD3
A
LD1
LD2
LD3
G
LD1
LD2
LD3
R
NORMAL OPERATION (RUN) MODE
ERROR MODE
Parameter Error
Error occurred when reading parameters from the
internal memory.
LD1
LD2
LD3
A
A
G
Overrange Input
The input is below -15% or above 115%.
LD1
LD2
LD3
R
G
G
G A
Burnout
PC Configuration RUN Mode
The transmitter is configured via PC and
is in normal operating conditions.
AD Conversion Error
Internal AD conversion error.
*
1. LD1 may be one of the
LD1
LD2
LD3
A
G
Output Limit
The output is at the upper or the lower limit.
Amber LED
Green LED
Red LED
OFF
ON
Blink
A
G
R
*
1
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit using the PC Configurator
Software (model: W2CFG).
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.