background image

W2XM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5504  Rev.3  P. 3 / 3

OUTPUT RANGING

The internal DIP switch setting is required to select output 
types before setting a precise output range using PC Con-
figurator Software (model: W2CFG).
For detailed information on the PC configuration, refer to 
the W2CFG users manual.

Table 1. DIP switch setting: Output 1 type

OUTPUT 1 TYPE

SW1-1

SW1-2

SW1-3

SW1-4

0 – 20 mA DC

OFF

OFF

ON

OFF

-10 – +10 V DC

OFF

ON

OFF

ON

-5 – +5 V DC

ON

OFF

OFF

ON

Table 2. DIP switch setting: Output 2 type

OUTPUT 2 TYPE

SW2-1

SW2-2

SW2-3

SW2-4

0 – 20 mA DC

OFF

OFF

ON

OFF

-10 – +10 V DC

OFF

ON

OFF

ON

-5 – +5 V DC

ON

OFF

OFF

ON

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Check DIP switch setting.
3) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

  If the potentiometer wires are broken, the output goes 

over 100% (below 0% with downscale) due to burnout 

function.  Confirm the status indicator LED pattern and 

check leadwires in such a case.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

6) LED:  Confirm that the LEDs indicate the normal operat-

ing mode.

STATUS INDICATOR LED

Combinations of the three front LEDs (LD1, LD2, LD3) indicate the transmitter’s operating status by different blinking pat-
terns.
Examples are shown below.

LD1

LD2

LD3

A

LD1

LD2

LD3

G

LD1

LD2

LD3

R

NORMAL OPERATION (RUN) MODE

ERROR MODE

Parameter Error
Error occurred when reading parameters from the 
internal memory.

LD1

LD2

LD3

A

A

G

Overrange Input
The input is below -15% or above 115%.

LD1

LD2

LD3

R

G

G

G A

Burnout

PC Configuration RUN Mode
The transmitter is configured via PC and 
is in normal operating conditions.

AD Conversion Error
Internal AD conversion error.

*

1. LD1 may be one of the

LD1

LD2

LD3

A

G

Output Limit
The output is at the upper or the lower limit.

Amber LED

Green LED

Red LED

OFF

ON

Blink

A

G

R

*

1

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit using the PC Configurator 
Software (model: W2CFG).

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.