M-system W2AP Скачать руководство пользователя страница 3

W2AP

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5535  Rev.7  P. 3 / 4

 

CONNECTION DIAGRAM

U(+)

V(–)

POWER

10

11

+

OUTPUT 1

7

8

+

3

6

OUTPUT 2

1

2

+

*

INPUT

R

The section enclosed by broken line is only with 2nd output option.

*

Input shunt resistor attached for current input.

■ 

Open Collector

Output Connection Examples 

+

7

8

+

■ 

Voltage Pulse

+

7

8

+

■ 

Dry Contact AC/DC Switch

• AC Powered

7

8

LOAD

Relay or 

Counter Coil

Varistor or Spark 

Quenching Circuit

• DC Powered

7

8

LOAD

Relay or 

Counter Coil

Spark Quenching

Diode

U

 

TERMINAL ASSIGNMENTS  unit: mm (inch)

4

8 7

10

11

5

6

3

9

INPUT RESISTOR

(model: REM2)

19 (.75)

1

2

Input shunt resistor attached
for current input.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

Отзывы: