EM-3220 Rev.6 P. 3 / 3
WIRING INSTRUCTIONS
■
EURO TYPE TERMINAL
Applicable wire size: 0.25 – 1.5 mm
2
Stripped length: 7 mm
PIPING
The pneumatic inlet is female screwed of Rc 1/4” (1/4” NPT
optional with a fitting). Tightening torque is at the maxi-
mum of 12 N·m. Check that there is no air leak at the con-
nection after sealing it.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that there is no air leak at the pneumatic
connection.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) =
Supply Voltage (V) – 12 (V)
0.02 (A)
(including leadwire resistance)
4) When you check the output signal, connect an ammeter
of which the internal resistance is of 10Ω max. to the
monitor terminals.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.