M-system SENTRONIC M2SES Скачать руководство пользователя страница 2

MODEL: M2SES

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

TERMINAL SCREW MATERIAL

/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Selecting operation: Automatic

INPUT SPECIFICATIONS

• DC Current: Input resistor incorporated

OUTPUT SPECIFICATIONS

• DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 15 V max.
• DC Voltage: -10 – +12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V

INSTALLATION

Power Consumption
•AC Power input:
 Approx. 3 VA at 100 V
 Approx. 4 VA at 200 V
 Approx. 5 VA at 264 V
•DC Power input: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span

Accuracy: ±0.2 %
Selecting sensitivity: 0.5%
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1000 V AC @1 minute (input to output)

2000 V AC @1 minute (input or output to power to ground)

STANDARDS & APPROVALS

CE conformity:
  EMC Directive (2004/108/EC)
  EN 61000-6-4 (EMI)
  EN 61000-6-2 (EMS)
  Low Voltage Directive (2006/95/EC)
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Max. operating voltage 300 V
  Input or output to power: Reinforced insulation
  Input to output: Basic insulation
Approval:
  UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D hazardous locations
  (UL 1604, CAN/CSA-C22.2 No.213)
  UL/C-UL general safety requirements
  (UL 61010B-1, CAN/CSA-C22.2 No.1010-1)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание SENTRONIC M2SES

Страница 1: ...DC Load resistance 1500 Ω max G 0 1 mA DC Load resistance 15 kΩ max Z Specify current See OUTPUT SPECIFICATIONS Voltage 1 0 10 mV DC Load resistance 10 kΩ min 2 0 100 mV DC Load resistance 100 kΩ min 3 0 1 V DC Load resistance 1000 Ω min 4 0 10 V DC Load resistance 10 kΩ min 5 0 5 V DC Load resistance 5000 Ω min 6 1 5 V DC Load resistance 5000 Ω min 4W 10 10 V DC Load resistance 10 kΩ min 5W 5 5 V...

Страница 2: ...rating temperature 5 to 55 C 23 to 131 F Operating humidity 30 to 90 RH non condensing Mounting Surface or DIN rail Weight 150 g 0 33 lbs PERFORMANCE in percentage of span Accuracy 0 2 Selecting sensitivity 0 5 Temp coefficient 0 015 C 0 008 F Response time 0 5 sec 0 90 Line voltage effect 0 1 over voltage range Insulation resistance 100 MΩ with 500 V DC Dielectric strength 1000 V AC 1 minute inpu...

Страница 3: ...een units 4 8 12 14 13 1 4 16 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation Base Socket Input shunt resistor incorporated for current inputs Selector Output Driver OUTPUT 9 12 U V POWER 1 INPUT 2 5 8 INPUT 1 4 13 14 Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Supp...

Страница 4: ...el The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe these re quirements may invalidate the CE UL conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V and 85 264V AC rating 85 264V 90 2...

Страница 5: ...bles are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 13 14 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that the load resistance meets the de scribed specifications EXTERNAL DIMENSIONS unit mm inch 5 9 21 5 85 70 5 2 78 84 3 31 10 39 15 59 6 23 59 2 32 DIN RAIL 35mm wide 4...