EM-1693  Rev.11  P. 5 / 7

HARDWARE SETTING & CALIBRATION

Sensitivity Adj. (V

H

)

Sensitivity Adj. (V

L

)

Sensor Excitation Adj.

O

N

2

1

3

4

5

6

7

8

Set each switch referring 

to the table below.

O

N

2

1

3

4

5

6

7

8

SW2

SW1

Set each switch referring 

to the table below.

(front cover open)

Input Monitor LED PL1
Input Monitor LED PL2

There is no need of hardware adjustment for RS-422 line driver pulse input.
Unnecessary switches or LEDs are not provided.

 

SW1 & 2 FUNCTIONS (SW1: Input 2, SW2: Input 1, SW1-3 and SW2-3 are used commonly to both inputs.)

SWITCH 

NO.

INPUT CODE

SW FUNCTION

A

B

C

D

H

SW1,2 - 1 ON with dry contact input (model suffix: A)

ON

OFF

OFF

OFF

OFF

2 ON with 2-wire current pulse input (model suffix: H)

OFF

OFF

OFF

OFF

ON

3 SW1-3: Adjustable range of sensitivity level for V

L

 

(ON: 0 – 10 V, OFF: 0 – 5 V)
SW2-3: Adjustable range of sensitivity level for V

L

 

(ON: 0 – 10 V, OFF: 0 – 5 V)
Refer to the section “SENSITIVITY ADJUSTMENT”.

ON or OFF 

(required level)

OFF

ON or 

OFF 

(required 

level)

OFF

4 Always ON

ON or OFF according to the adjustment

5 Noise filter Type 1 (ON: with, OFF: without)

ON or OFF according to the noise level.
Refer to the tables below for the max.
frequency which can pass through the filter.

6 Noise filter Type 2 (ON: with, OFF: without)

7 Attenuator for input signal (ON: with, OFF: without)

Input voltage is attenuated to half the original amplitude with this switch ON.
(one-third for the model number suffix code A.)

OFF*

OFF*

OFF

OFF*

OFF

8 Input pulse sensing method (ON: DC coupled, OFF: AC coupled)

Turn this switch off with a 10 V or greater offset.

ON

*Set to ON with excitation voltage ≥ 24 V.

 

INPUT FILTER

The tables below show the maximum frequency which can pass through the filter when the sensitivity level is set to 2 V.  The 
frequency may change according to the sensitivity level.
After turning the filter ON, check that the PL1 and PL2 blink according to the input signals.  If they do not, readjust the 
sensitivity according to the instructions in the following section.

• Noise Filter Type 1 (SW1/2-5 = ON)

DC Coupling
(SW1/2-8 = ON)

AC Coupling
(SW1/2-8 = OFF)

V p-p (V)

MAX. FREQ. (Hz)

V p-p (V)

MAX. FREQ. (Hz)

5

69

5

22

12

35

12

65

24

89

24

112

• Noise Filter Type 2 (SW1/2-6 = ON)

DC Coupling
(SW1/2-8 = ON)

AC Coupling
(SW1/2-8 = OFF)

V p-p (V)

MAX. FREQ. (Hz)

V p-p (V)

MAX. FREQ. (Hz)

5

1220

5

256

12

329

12

664

24

851

24

1090

Содержание RPPD

Страница 1: ...ments in regard to the whole system and employ additional protective measures to ensure the CE conform ity Install lightning surge protectors for those wires connect ed to remote locations For 24V DC...

Страница 2: ...nput Monitor LED PL2 Input Monitor LED PL1 INSTALLATION Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket DIN RAIL MOUNTING Set the base soc...

Страница 3: ...2 9 6 5 SENSOR EXC OUTPUT 1 1 2 U V POWER 7 8 3 4 5 6 OUTPUT 2 10 11 ROTARY ENCODER Input Connection Examples Open Collector Output Connection Examples Voltage Pulse Power Photo MOSFET Relay AC Power...

Страница 4: ...I O PULSE LOGIC VOLTAGE PULSE or RS 422 LINE DRIVER PULSE OUTPUT WAVEFORM OPEN COLLECTOR or POWER PHOTO MOSFET RELAY The pulse width in one shot means the bold lined section of a pulse waveform Pulse...

Страница 5: ...ON ON or OFF according to the adjustment 5 Noise filter Type 1 ON with OFF without ON or OFF according to the noise level Refer to the tables below for the max frequency which can pass through the fil...

Страница 6: ...SW1 2 5 or SW1 2 6 3 Connect the positive probe to the test hole No 2 and turn the VH potentiometer until the meter shows desired val ue 1 4 Connect the positive probe to the test hole No 3 and turn t...

Страница 7: ...mitter may fail 25 5 12 24 60 120 CURRENT mA VOLTAGE V Voltage V Current A 600mW MAINTENANCE TROUBLESHOOTING Refer to the flow chart below Checking Maintenance To TERMINAL CONNECTIONS End of Checking...

Отзывы: