WIRING INSTRUCTIONS
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable.
• M3 Screw (Modbus and current input)
Applicable wire size: 0.25 to 1.65 mm
2
(AWG22 to 16)
Torque: 0.5 N∙m
3.3 max. (.13)
6 max.
(.24)
mm (inch)
• M3.5 Screw (auxiliary power and voltage input)
Applicable wire size: 1.04 to 2.63 mm
2
(AWG16 to 14)
Torque: 0.8 N∙m
3.8 max. (.15)
7 max.
(.28)
mm (inch)
COMMUNICATION CABLE CONNECTIONS
Tx+/Rx+
SG
Rx+
Rx−
Host PC
DA
DB
DG
SLD
FE
Remote Unit
DA
DB
DG
SLD
FE
Remote Unit
TERMINATOR
TERMINATOR
Be sure to connect the terminating resistor across DA and DB at both ends of communication line.
When this unit is located at an end, turn the terminating resistor SW ON.
The Host PC can be located at not only both ends but also any node of the of communication line.
■
MASTER CONNECTION
Tx−/Rx−