MODEL: R8-NEIP1

R8-NEIP1 SPECIFICATIONS

ES-9799 Rev.0   Page 2/5

http://www.m-system.co.jp/

1.6 A)
Internal power supply (power supply for I/O module):
• DC power supply: 5 V DC
• Current capacity: 1.6 A
Excitation supply output (excitation for I/O module)
•DC: 24 V DC ±10 %
•Operational current: 10 A
 (From power supply (exitation supply) connector, via
connector for internal bus, supplied to each I/O module.
Power output current consumption must be under
operational current.)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 180 g (0.40 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(EthrtNet/IP to internal bus or internal power or power input
to excitation supply to FE1)

STANDARDS & APPROVALS

EU conformity:
EMC Directive
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive