R7ML-TS4
P. 3 / 10
EM-7805-B Rev.7
■
STATUS INDICATOR LED
ID
COLOR
FUNCTION
PWR
Green
Turns on when the internal 5V is supplied
normally.
RUN
Green
Turns on in normal communications
conditions.
ERR
Red
Turns on in no communication or setting
error.
SD
Green
Turns on when the module is transmitting.
RD
Green
Turns on when the module is receiving.
■
STATION ADDRESS
Station Address is selected between 60H and 7FH (Intel-
ligent I/O) in hexadecimal. (Certain numbers may not be
selectable depending on the master types. Refer to the in-
struction manual of the master unit.)
The left switch determines the MSD, while the right switch
does the LSD of the address.
(Factory setting: 60H)
Station Address Setting (LSD)
Station Address Setting (MSD)
89AB
C
D
EF0
123
45
67
89AB
C
D
EF0
123
45
67
■
MECHATROLINK MODE
Choose MECHATROLINK-I or -II, and the data size. Posi-
tions 2, 4 through 9 are unused.
(Factory setting: 1)
5
4
3
2
1
0
9
8
7
6
MECHATROLINK Setting
0 : MECHATROLINK-II (32-byte mode)
1 : MECHATROLINK-II (17-byte mode)
3 : MECHATROLINK-I (17-byte mode)
■
EXTENSION MODULE
Combinations with any extension module is selectable.
■
OPERATING MODE
(*) Factory setting
• Extension (SW1-1, 1-2)
SW1-1
SW1-2
EXTENSION
OFF
OFF
No extension (*)
ON
OFF
Discrete input, 8 or 16 points
OFF
ON
Discrete output, 8 or 16 points
• Conversion Rate (SW1-3)
SW1-3
CONVERSION RATE
OFF
250 msec. (*)
ON
1 sec.
• Burnout (SW1-4)
SW1-4
BURNOUT
OFF
Upscale (*)
ON
Downscale
• Thermocouple Type (SW1-5, 1-6, 1-7, 1-8)
SW1-5
SW1-6
SW1-7
SW1-8 THERMOCOUPLE TYPE
OFF
OFF
OFF
OFF
K (CA) (*)
ON
OFF
OFF
OFF
E (CRC)
OFF
ON
OFF
OFF
J (IC)
ON
ON
OFF
OFF
T (CC)
OFF
OFF
ON
OFF
B (RH)
ON
OFF
ON
OFF
R
OFF
ON
ON
OFF
S
ON
ON
ON
OFF
C (WRe 5-26)
OFF
OFF
OFF
ON
N
ON
OFF
OFF
ON
U
OFF
ON
OFF
ON
L
ON
ON
OFF
ON
P (Platinel II)
OFF
OFF
ON
ON
(PR)
ON
ON
ON
ON
PC Configurator setting
■
PC CONFIGURATOR JACK
Analog input modules are equipped with the PC Configura-
tor Jack.
The PC Configurator is used to set the following parameters
for each channel.
• Zero and span adjustments
• Scaling (factory default: engineering unit conversion (°C))
• Conversion rate (factory default: 500 msec.)
• Sensor type and range
Before starting programming, turn on the front SW1-5, 6 ,7,
8. For more information about the programming using the
R7CON, please refer to the R7CON Users Manual.
■
POWER SUPPLY TERMINAL ASSIGNMENT
4
NC
5
NC
6
+24V
1
NC
2
NC
3
FG
7
0V
NO.
ID
FUNCTION, NOTES
1
NC
----
2
NC
----
3
FG
FG
4
NC
----
5
NC
----
6
+24V
Power input (24V DC)
7
0V
Power input (0V)
■
INPUT TERMINAL ASSIGNMENT
10
+IN0
11
–IN0
12
+IN1
1
+CJ0
2
–CJ0
3
+CJ1
13
–IN1
4
–CJ1
14
NC
5
NC
15
+IN2
6
+CJ2
16
–IN2
7
–CJ2
17
+IN3
8
+CJ3
9
–CJ3
18
–IN3
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
+CJ0 CJC 0
10
+IN0 T/C + 0
2
–CJ0 CJC 0
11
–IN0 T/C – 0
3
+CJ1 CJC 1
12
+IN1 T/C + 1
4
–CJ1 CJC 1
13
–IN1 T/C – 1
5
NC
No connection