R7ML-DC16D

P. 3 / 10

EM-7805-X Rev.1

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Green

Turns on when the internal 5V is supplied
normally.

RUN

Green

Turns on in normal communications
conditions.

ERR

Red

Turns on in no communication or setting
error.

SD

Green

Turns on when the module is transmit-
ting.

RD

Green

Turns on when the module is receiving.

 

STATION ADDRESS

Station Address is selected between 60H and 7FH (Intel-
ligent I/O) in hexadecimal.  (Certain numbers may not be 
selectable depending on the master types.  Refer to the in-
struction manual of the master unit.)
The left switch determines the MSD, while the right switch 
does the LSD of the address.
(Factory setting: 60H)

Station Address Setting (LSD)

Station Address Setting (MSD)

89AB

C

D

EF0

123

45

67

89AB

C

D

EF0

123

45

67

 

MECHATROLINK MODE

Choose MECHATROLINK-I or -II, and the data size.  Posi-
tions 2, 4 through 9 are unused.
(Factory setting: 1)

5

4

3

2

1

0

9

8

7

6

MECHATROLINK Setting

0 : MECHATROLINK-II  (32-byte mode)
1 : MECHATROLINK-II  (17-byte mode)
3 : MECHATROLINK-I  (17-byte mode)

 

EXTENSION MODULE

Combinations with any extension module is selectable.

 

OPERATING MODE

(*) Factory setting

• 

Extension (SW1-1, 1-2)

SW1-1

SW1-2

Extension

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• 

Output at the loss of communication (SW1-4)

SW1-4

Output at the loss of communication

OFF

Reset the output (turned off)

ON

Hold the output (*)
(maintains the last data received normally)

Caution ! -  SW1-3, 1-5, 1-6, 1-7, 1-8 are unused. Be sure to turn 

off unused ones.

 

DISCRETE OUTPUT STATUS INDICATOR LED

Discrete output modules have LED indicators showing out-
put signal status.
     

Contact ON : LED ON

     

Contact OFF : LED OFF

 

POWER SUPPLY TERMINAL ASSIGNMENT

4

NC

5

NC

6

+24V

1

NC

2

NC

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

NC

----

2

NC

----

3

FG

FG

4

NC

----

5

NC

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

OUTPUT TERMINAL ASSIGNMENT

10

+24 V

11

Y1

12

Y3

1

0 V

2

Y0

3

Y2

13

Y5

4

Y4

14

Y7

5

Y6

15

Y9

6

Y8

16

YB

7

YA

17

YD

8

YC

9

YE

18

YF

NO.

ID

FUNCTION

NO.

ID

FUNTION

1

0V

0V

10

+24V 24V DC (common)

2

Y0

Output 0

11

Y1

Output 1

3

Y2

Output 2

12

Y3

Output 3

4

Y4

Output 4

13

Y5

Output 5

5

Y6

Output 6

14

Y7

Output 7

6

Y8

Output 8

15

Y9

Output 9

7

YA

Output 10

16

YB

Output 11

8

YC

Output 12

17

YD

Output 13

9

YE

Output 14

18

YF

Output 15

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7ML-DC16D

Страница 1: ...rements in regard to the whole system and employ additional protective measures to ensure CE conformity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 85mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety ENVIRONM...

Страница 2: ...8 9 6 14 5 MECHATROLINK Setting Rotary SW MECHATROLINK Connector Station Address Setting Rotary SW Status Indicator LED Operating Mode Setting DIP SW SW1 PC Configurator Jack Discrete Output Status Indicator LED Power Supply Terminals MECHATROLINK Connector Output Terminals LEFT SIDE VIEW FRONT VIEW 89A B C D E F 0 1 2 3 4 5 6 7 89A B C D E F 0 1 2 3 4 5 6 7 056 222 38 18 mailbox sentronic com www...

Страница 3: ...with any extension module is selectable OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 Extension OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Output at the loss of communication SW1 4 SW1 4 Output at the loss of communication OFF Reset the output turned off ON Hold the output maintains the last data received normally Caution SW1 3 ...

Страница 4: ... diagram below Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal 24V DC EXTENSION CONNECTOR Output Connection Example 10 17 18 1 YD 16 YB 0V YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 24V Y0 2 10 1 2 Y0 0V 24V 18 YF 7 6 3 0V FG MECHATROLINK CONNECTOR MECHATROLINK CONNECTOR MECHATROLINK connect...

Страница 5: ...ave SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD MECHATROLINK Cable MECHATROLINK Cable MECHATROLINK COMMUNICATION MECHATROLINK I Baud rate 4 Mbps Transmission distance 50 m max Distance between stations 30 cm min Transmission media MECHATROLINK cable Model JEPMC W6003 x E Yaskawa Controls Co Ltd Max number of slaves 15 The maximum number of slaves might change depending on the master unit Refer to th...

Страница 6: ...0 0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK II in the 17 byte mode CDRW Command 03H Data Format Byte COMMAND RESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to CDRW 1 CMD RCMD CMD Application...

Страница 7: ... RESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to CDRW 1 ID_RD 03H ID_RD 03H Read ID ID_RD Command Read out the device ID 2 0 ALARM Error code See MECHATROLINK DATA DESCRIPTIONS 3 0 STATUS1 Status code See MECHATROLINK DATA DESCRIPTIONS 4 0 STATUS2 Status code See MECHATROLINK DATA DESCRIPTIONS 5 DEVICE_ CODE DEVICE_ COD...

Страница 8: ...sion cycle 8 0 0 9 0 0 10 0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK II in the 17 byte mode DISCONNECT Command 0FH Data Format Byte COMMAND RESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to C...

Страница 9: ...alid Command Command is not supported Warning 02H Command Not Allowed Command execution conditions are not met Warning 03H Invalid Data Data in the command is not correct Warning 04H Synchronization Error Alarm STATUS1 Bit Allocations Alarm Warning classification and status information are set at STATUS1 in the response and sent to the master Bit DEFINITION DESCRIPTION 0 Alarm Bit 0 Normal 1 Alarm...

Страница 10: ...dule output data in the command are repeated and sent back to the master ID DESCRIPTION REMARKS EXT IN LO Extension data low 8 bits R7ML EA16 R7ML EA8 Bit 0 through 7 data are set R7ML EC16x R7ML EC8x Output data are repeated EXT IN HI Extension data high 8 bits R7ML EA16 Bit 8 through 15 data are set R7ML EC16x Output data are repeated R7ML EA8 R7ML EC8x Unused Extension Output Data Output data t...

Отзывы: