background image

R7M-SV4

P. 2 / 7

EM-7803-A Rev.6

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Modbus, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
normally.

RUN

Red

Turns on when the data is received nor-
mally.

ERR

Red

Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The 
left switch determines the tenth place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

 

OPERATING MODE

(*) Factory setting

• 

Extension (SW1-1, 1-2)

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• 

Conversion Rate / Accuracy (SW1-3, 1-4)

SW1-3

SW1-4 CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.1% (*)

ON

OFF

40 msec. / ±0.2%

OFF

ON

20 msec. / ±0.4%

ON

ON

10 msec. / ±0.8%

• 

Input Range (SW1-5, 1-6, 1-7, 1-8)

SW1-5

SW1-6

SW1-7

SW1-8 INPUT RANGE

OFF

OFF

OFF

OFF

-10 – +10V DC (*)

ON

OFF

OFF

OFF

-5 – +5V DC

OFF

ON

OFF

OFF

-1 – +1V DC

ON

ON

OFF

OFF

0 – 10V DC

OFF

OFF

ON

OFF

0 – 5V DC

ON

OFF

ON

OFF

1 – 5V DC

OFF

ON

ON

OFF

0 – 1V DC

ON

ON

ON

OFF

-0.5 – +0.5V DC

ON

OFF

OFF

ON

-20 – +20mA DC

OFF

ON

OFF

ON

4 – 20mA DC

ON

ON

OFF

ON

0 – 20mA DC

ON

ON

ON

ON

PC Configurator setting

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

----

2

SLD

Shield

3

FG

FG

4

DA

----

5

DG

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

VL0

11

I0

12

VL1

1

VH0

2

COM0

3

VH1

13

I1

4

COM1

14

NC

5

NC

15

VL2

6

VH2

16

I2

7

COM2

17

VL3

8

VH3

9

COM3

18

I3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

VH0 Wide span volt. 0 10

VL0 Narrow span volt. 0

2 COM0 Common 0

11

I0

Current range 0

3

VH1 Wide span volt. 1 12

VL1 Narrow span volt. 1

4 COM1 Common 1

13

I1

Current range 1

5

NC

No connection

14

NC

No connection

6

VH2 Wide span volt. 2 15

VL2 Narrow span volt. 2

7 COM2 Common 2

16

I2

Current range 2

8

VH3 Wide span volt. 3 17

VL3 Narrow span volt. 3

9 COM3 Common 3

18

I3

Current range 3

 

INPUT RANGE

• 

Wide span

 : –10 to +10V DC,  –5 to +5V DC,  0 to 10V DC,  

0 to 5V DC,  1 to 5V DC

• 

Narrow span

: –1 to +1V DC,  0 to 1V,  –0.5 to +0.5V DC

• 

Current input

: –20 to +20mA DC, 0 to 20mA DC, 

4 to 20mA DC

Содержание R7M-SV4

Страница 1: ... to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this unit when it is integrat ed in a panel system The user may have to review the CE requirements in regard...

Страница 2: ...ectable OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Conversion Rate Accuracy SW1 3 1 4 SW1 3 SW1 4 CONVERSION RATE ACCURACY OFF OFF 80 msec 0 1 ON OFF 40 msec 0 2 OFF ON 20 msec 0 4 ON ON 10 msec 0 8 Input Range SW1 5 1 6 1 7 1 8 SW1 5 SW1 6 SW1 7 SW1 8 INPUT RANGE OFF OFF O...

Страница 3: ...or terminal WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Communication cable Applicable wire size 0 2 to 0 5 mm2 AWG26 22 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Others 0 25 to 1 65 m...

Страница 4: ...d cautions when installing R7M are stated below Use control panels with an internal panel plate both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG term...

Страница 5: ... using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install th...

Страница 6: ...Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the co...

Страница 7: ...m is not effective Points of cautions applicable when wiring the R7M Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via Modbus ground the cable shield using an earth clamp Ke...

Отзывы: