background image

R7M-MS4

P. 2 / 7

EM-7803-Q Rev.3

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Modbus, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
normally.

RUN

Red

Turns on when the data is received nor-
mally.

ERR

Red

Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

 

OPERATING MODE

(*) Factory setting

•  

Extension (SW1-1, 1-2)

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

•  

Conversion Rate / Accuracy (SW1-3, 1-4)

SW1-3

SW1-4 CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.1% (*)

ON

OFF

40 msec. / ±0.2%

OFF

ON

20 msec. / ±0.4%

ON

ON

10 msec. / ±0.8%

Note : Be sure to set unused SW1-5 through 1-8 to OFF.

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

----

2

SLD

Shield

3

FG

FG

4

DA

----

5

DG

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

H0

11

S0

12

H1

1

NC

2

L0

3

NC

13

S1

4

L1

14

NC

5

NC

15

H2

6

NC

16

S2

7

L2

17

H3

8

NC

9

L3

18

S3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

H0

Pot H0

2

L0

Pot L0

11

S0

Pot S0

3

NC

No connection

12

H1

Pot H1

4

L1

Pot L1

13

S1

Pot S1

5

NC

No connection

14

NC

No connection

6

NC

No connection

15

H2

Pot H2

7

L2

Pot L2

16

S2

Pot S2

8

NC

No connection

17

H3

Pot H3

9

L3

Pot L3

18

S3

Pot S3

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7M-MS4-R

Страница 1: ...lightning surge protectors for those wires connect ed to remote locations Choose a surge protector with its maximum surge voltage 40V or less between lines Rec ommended M System model MDP D24 POWER IN...

Страница 2: ...AUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 38 4 kbps factory setting 1 19 2 kbps 2 9600 bps 3 4800 bps EXTENSION MODULE Combinations with all extensi...

Страница 3: ...ETER max min EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal WIRING INSTRUCTIONS SCREW TERMINAL Torque...

Страница 4: ...g R7M are stated below Use control panels with an internal panel plate both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a t...

Страница 5: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 6: ...ons are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to th...

Страница 7: ...us Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To conn...

Отзывы: