R7M-DC4G

EM-7803-BB  P. 2 / 4

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

X10

X1

NODE ADD.

B.RATE

CNFG.

1 2 3 4 5 6 7 8

0 1 2 3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

ERR

RD

RUN

SD

PWR

4

5

6

7

1

2

3

(A)

(F)

(H)

(G)

(B)

(C)

(D)

(E)

LEFT SIDE VIEW

TERM

ON

OFF

(I)

(A) Status Indicator LED
(B) Station Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operation Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) Discrete Output Status Indicator LED
(G) Modbus, Power Supply Terminal
(H) Output Terminals
(I) Terminating Resistor SW

FRONT VIEW

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is sup-
plied normally.

RUN

Red

Turns on when the data is received 
normally.

ERR

Red

Turns on when the received data is ab-
normal.  Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmit-
ting.

RD

Red

Turns on when the module is receiving.

 

DISCRETE OUTPUT STATUS INDICATOR LED

LED red indicators show the signal status.

ON  : a contact output (NO)
OFF : b contact output (NC)

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.
(Factory setting 0).

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps

5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps

 

OPERATING MODE

• Output at the Loss of Communication: SW1-4

SW1-4

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

B contact output
(Discard the last data received normally)

ON

Hold the output (*)
(maintains the last data received normally)

(*) Factory setting
Note:  Be sure to set unused SW1-1 through 1-3 and 1-5 

through 1-8 to OFF.

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

6

7

1

2

3

DG +24V

0V

DB

SLD

FG

(1)  DB 

(2)  SLD 

Shield

(3)  FG 

FG

(4)  DA 

(5)  DG 

(6)  +24V 

Power input (24V DC)

(7)  0V 

Power input (0V)

 

OUTPUT TERMINAL ASSIGNMENT

10

+24V

11

Y0

12

Y1

1

0V

2

COM0

3

COM0

13

Y2

4

COM0

14

Y3

5

COM0

15

Y4

6

COM1

16

Y5

7

COM1

17

Y6

8

COM1

9

COM1

18

Y7

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

0V

0V 

10

+24V 24V DC

2

COM0 Output common 0

11

Y0

Output 0 (NO)

3

COM0 Output common 0

12

Y1

Output 0 (NC)

4

COM0 Output common 1

13

Y2

Output 1 (NO)

5

COM0 Output common 1

14

Y3

Output 1 (NC)

6

COM1 Output common 2

15

Y4

Output 2 (NO)

7

COM1 Output common 2

16

Y5

Output 2 (NC)

8

COM1 Output common 3

17

Y6

Output 3 (NO)

9

COM1 Output common 3

18

Y7

Output 3 (NC)

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and
OFF to invalidate.
(Factory setting OFF)

 

EXTENSION MODULE

Combinations with all extension modules are available

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG