manualshive.com logo in svg
background image

EM-7803-AK  Rev.4  P. 1 / 8

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Discrete I/O module ............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and

confirm its operational range as indicated below:

24V DC rating: 24V ±10%, approx. 40mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply, input and output signal for safety.

• Before you remove the terminal block or mount it, turn

off the power supply, input and output signal for safety.

• DO NOT set the switches on the module while the power

is supplied.  The switches are used only for maintenance
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C

(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.

• Be sure to close the terminal cover for safety.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet

NPN DISCRETE INPUT & NPN TRANSISTOR OUTPUT 

MODULE, 8 points each

(Modbus 115.2 kbps)

MODEL

R7M-DAC16C

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7M-DAC16C-R

Страница 1: ...ange as indicated below 24V DC rating 24V 10 approx 40mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply input and output signal for safety Before you remove the t...

Страница 2: ...actory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch Factory setting 0 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 38 4 kbps 1 19 2 kbps 2 9600 bps 3 4800 bps...

Страница 3: ...ut 3 8 Y4 Output 4 17 Y5 Output 5 9 Y6 Output 6 18 Y7 Output 7 TERMINATING RESISTOR To use the terminating resistor turn the switch ON and OFF to invalidate Factory setting OFF EXTENSION MODULE Combin...

Страница 4: ...ALS for Modbus POWER 18 M3 SCREW TERMINALS for I O 6 24 6 24 CONNECTION DIAGRAM Note In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conducto...

Страница 5: ...mbined to realize momentary switching with one shot output Bit 0 2 4 6 are used to control each set of outputs while Bit 1 3 5 7 are unused An example of Bit 0 controlling Y0 and Y1 outputs sequential...

Страница 6: ...shot output 1 Unused 2 Y2 1 One shot output Y3 0 One shot output 3 Unused 4 Y4 1 One shot output Y5 0 One shot output 5 Unused 6 Y6 1 One shot output Y7 0 One shot output 7 Unused 8 Unused 9 Unused 1...

Страница 7: ...e type RUN status Exception Codes CODE NAME 01 Illegal Function Function code is not allowable for the slave 02 Illegal Data Address Address is not available within the slave 03 Illegal Data Value Dat...

Страница 8: ...drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG...

Отзывы: