R7M-CT4E

P. 2 / 7

EM-7803-R Rev.3

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Modbus, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
ormally.

RUN

Red

Turns on when the data is received nor-
mally.

ERR

Red

Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

 

OPERATING MODE

(*) Factory setting

•  Extension (SW1-1, 1-2)

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

•  Conversion Rate / Accuracy (SW1-3, 1-4)

SW1-3

SW1-4 CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.5% (*)

ON

OFF

40 msec. / ±0.5%

OFF

ON

20 msec. / ±1.0%

ON

ON

10 msec. / ±2.0%

•  Input Range (SW1-5, 1-6, 1-7, 1-8)

SW1-5

SW1-6

SW1-7

SW1-8 INPUT RANGE

OFF

OFF

OFF

OFF

CLSE-60 (*)

ON

OFF

OFF

OFF

CLSE-40

OFF

ON

OFF

OFF

CLSE-20

ON

ON

OFF

OFF

CLSE-10

OFF

OFF

ON

OFF

CLSE-05

ON

OFF

ON

OFF

CLSE-R5

ON

ON

ON

ON

PC Configurator setting

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

----

2

SLD

Shield

3

FG

FG

4

DA

----

5

DG

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

K0

11

L0

12

K1

1

NC

2

NC

3

NC

13

L1

4

NC

14

NC

5

NC

15

K2

6

NC

16

L2

7

NC

17

K3

8

NC

9

NC

18

L3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

K0

AC current K0

2

NC

No connection

11

L0

AC current L0

3

NC

No connection

12

K1

AC current K1

4

NC

No connection

13

L1

AC current L1

5

NC

No connection

14

NC

No connection

6

NC

No connection

15

K2

AC current K2

7

NC

No connection

16

L2

AC current L2

8

NC

No connection

17

K3

AC current K3

9

NC

No connection

18

L3

AC current L3

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7M-CT4E-R

Страница 1: ...ormity Install lightning surge protectors for those wires connect ed to remote locations Choose a surge protector with its maximum surge voltage 40V or less between lines Rec ommended M System model MDP D24 POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 100mA GENERAL PRECAUTIO...

Страница 2: ...9600 bps 3 4800 bps EXTENSION MODULE Combinations with all extension modules are selectable OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Conversion Rate Accuracy SW1 3 1 4 SW1 3 SW1 4 CONVERSION RATE ACCURACY OFF OFF 80 msec 0 5 ON OFF 40 msec 0 5 OFF ON 20 msec 1 0 ON ON 10 ...

Страница 3: ...NSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Communica...

Страница 4: ...ng R7M are stated below Use control panels with an internal panel plate both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module t...

Страница 5: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7M Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Страница 6: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the imp...

Страница 7: ...atus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via Modbus ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic ...

Отзывы: