R7L-DC16B
EM-7804-H Rev.7 P. 17 / 19
■
FUNCTIONAL BLOCK: fbDOEX[0...7]
• Network Properties
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nviDOEX1
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Turns on or off Y0, Y2, Y4, Y6, Y8, YA, YC, YE of the extension module
depending upon this input.
100.0 1 : ON
Other : OFF
nviDOEX2
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Turns on or off Y1, Y3, Y5, Y7, Y9, YB, YD, YF of the extension module
depending upon this input.
100.0 1 : ON
Other : OFF
• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTdirection
----
{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}
Bit 1: Output held or not at power off
0 : OFF at the power startup
1 : Outputs the held status at the power startup
Bit 0, Bit 2 through 15 : Invalid
SCPTpwrUpState
nviDOEX1
{SNVT_switch}
{0.0 0}, {100.0 1},
{Invalid}
{0.0 0}
Set value applied at nviDOEX1 when the power supply is
turned on.
SCPTpwrUpState
nviDOEX2
{SNVT_switch}
{0.0 0}, {100.0 1},
{Invalid}
{0.0 0}
Set value applied at nviDOEX2 when the power supply is
turned on.
056 222 38 18
www.sentronic.com
SENTRONIC
AG