I/O DATA DESCRIPTION

 

DISCRETE OUTPUT MODULE

0

15

Output 0
Output 1
Output 2
Output 3

Output 15

0: OFF   1: ON

Output 7
Output 8

Output 16
Output 17
Output 18
Output 19

Output 31

Output 23
Output 24

 DISCRETE OUTPUT

 STATUS

0

15

Output 0 

Output 16 (Overcurrent/overheat; disconnection)

Output 1 

Output 17 (Overcurrent/overheat; disconnection)

Output 2 

Output 18 (Overcurrent/overheat; disconnection)

Output 3 

Output 19 (Overcurrent/overheat; disconnection)

Output 7 

Output 23 (Overcurrent/overheat; disconnection)

Output 8 

Output 24 (Overcurrent/overheat; disconnection)

Output 4 

Output 20 (Overcurrent/overheat; disconnection)

Output 5 

Output 21 (Overcurrent/overheat; disconnection)

Output 6 

Output 22 (Overcurrent/overheat; disconnection)

Output 11   Output 27 (Overcurrent/overheat; disconnection)
Output 12   Output 28 (Overcurrent/overheat; disconnection)

Output 9 

Output 25 (Overcurrent/overheat; disconnection)

Output 10   Output 26 (Overcurrent/overheat; disconnection)

Output 14   Output 30 (Overcurrent/overheat; disconnection)
Output 15  Output 31 (Overcurrent/overheat; disconnection)

Output 13   Output 29 (Overcurrent/overheat; disconnection)

0 : Normal
1 : Detected the overcurrent/overheat and disconnection

Note: Status is disabled with option code /D1 (without wire breakdown detection).

When overcurrent or overheat is detected on each channel of discrete output while the output is ON, the status bit correspond-
ing to the output turns “1” and is latched*.  Then the discrete output is also latched to OFF.
To reset the latched bit and discrete output, set this output to OFF  from the host PC/PLC or turn off and on the power supply 
to the unit.
When disconnection (open load) is detected while output is OFF, the corresponding status bit turns “1” but is not latched.

*  The status bit turns “0” if the load is opened in the state overcurrent or overheat is detected.  However, the discrete output of the 

unit remains latched.  Be sure to remove the cause of error and reset the latched output by setting the output to OFF or turning 
off/on the power supply. 

Содержание R7I4DML3-DC32A

Страница 1: ...filters and clamp fil ters for the power source input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its oper...

Страница 2: ...INDICATOR LED ID COLOR FUNCTION PWR Green Turns on when the internal power is sup plied normally ERR Red Turns on at MECHATROLINK III com munication error CON Green Turns on at MECHATROLINK III con n...

Страница 3: ...Output 28 Y15 1 24V 24V DC Y1D 1 24V 24V DC 2 NC Unused 2 NC Unused 3 NC Unused 3 NC Unused 4 Y15 Output 21 4 Y1D Output 29 Y16 1 24V 24V DC Y1E 1 24V 24V DC 2 NC Unused 2 NC Unused 3 NC Unused 3 NC...

Страница 4: ...A1 5 10 1 5 mm2 Phoenix Contact 1 2 3 4 5 1 PWR 2 PWR 3 FE 4 SNSR EXC 5 SNSR EXC Power Supply Power Supply Functional earth Sensor excitation Sensor excitation Note The numbers marked on the connector...

Страница 5: ...e DIN rail mounter slider with tip of a mi nus screwdriver 2 Pull the lower of the unit 3 Remove the upper hook of the unit from the DIN rail 3 1 2 SURFACE MOUNTING 1 Insert the two DIN rail mounter s...

Страница 6: ...rminal is NOT a protective conductor terminal SNSR EXC SNSR EXC FE PWR PWR 1 2 4 5 3 POWER SUPPLY IN SENCOR EXCITATION IN SNSR EXC SNSR EXC FE PWR PWR 1 2 4 5 3 POWER SUPPLY OUT SENCOR EXCITATION OUT...

Страница 7: ...arning command ALM_CLR 06H Clear alarm or warning command CONNECT 0EH Establish connection command DISCONNECT 0FH Release connection command Standard I O profile DATA_RWA 20H Transmit I O data NOP 00H...

Страница 8: ..._STAT 3 4 0000H 0000H Clear current alarm or warning Other than 0000H is not available 5 6 00H 00H Reserve CONNECT 0EH Starts communication with master station BYTE COMMAND RESPONSE REMARKS 0 CONNECT...

Страница 9: ...0 through 7 of the data which reads back the output data are set CH0 IN HI CH0 data high 8 bits Bit 8 through 15 of the data which reads back the output data are set CH1 IN LO CH1 data low 8 bits Bit...

Страница 10: ...ed 1 D_WAR Not used 2 CMDRDY 1 Command reception enabled 0 Other 3 ALM_CLR_CMP 1 Completion of execution of ALM_CLR 0 Other ALM_CLR_CMP can be canceled by setting 0 for ALM_CLR in CMD_CTRL command are...

Страница 11: ...sec 17H Max Transmission Cycle 4 Yes 0x0061A800 64 msec 18H Increments of Transmission Cycle 4 Yes 0x00000001 Available to 31 25 62 5 125 250 500 sec 1 64 msec 1 msec increments 19H Min Communication...

Страница 12: ...ction Output 9 Output 25 Overcurrent overheat disconnection Output 10 Output 26 Overcurrent overheat disconnection Output 14 Output 30 Overcurrent overheat disconnection Output 15 Output 31 Overcurren...

Отзывы: