background image

R7F4DC-DAC16C-H

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7767-G  P. 7 / 8

MOUNTING REQUIREMENTS  

unit: mm [inch]

125 [4.92]

2-M4

DATA ALLOCATION

F

0

1F

F

0

1F

RX (n+0) 7 – RX (n+0) 0

Unused

RY (n+0) F – RY (n+0) 8

Unused

Interval timed Response (X)

Refresh Data (Y)

I/O DATA DESCRIPTIONS

 DISCRETE I/O

0

15

Input 0
Input 1
Input 2
Input 3

Input 7
Unused

Unused

0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON

0: OFF / 1: ON

:

:

:

:

:

:

:

:

:

0

15

Unused
Unused
Unused
Unused

Unused
Output 8

Output 15

0: OFF / 1: ON

0: OFF / 1: ON

:

:

:

:

:

:

:

:

:

Содержание R7F4DC-DAC16C-H

Страница 1: ... source input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 30 mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and I O signal for safety Before you remove the connector or mount it make sure to turn ...

Страница 2: ...dule is receiving 1 Run LED turns off when no command is received from the master device DISCRETE I O STATUS INDICATOR LED Green LED shows the I O status ON LED ON OFF LED OFF STATION ADDRESS The left switch determines the tenth place digit while the right one does the ones place digit of the station address 1 64 Factory setting 00 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Station Address Setting x1...

Страница 3: ...ent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed or power supply failure OFF OFF ON ON BL Blinking 1 SD LED which is blinking may appear to be ON with high baud rate especially when fewer modules are connected 2 LED combinations indicated with do not occur...

Страница 4: ...Unused 4 X0 Input 0 4 Y8 Output 8 X1 1 24V 24V DC Y9 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 NC Unused 4 X1 Input 1 4 Y9 Output 9 X2 1 24V 24V DC YA 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 NC Unused 4 X2 Input 2 4 YA Output 10 X3 1 24V 24V DC YB 1 24V 24V DC 2 NC Unused 2 NC Unused 3 GND 0V 3 NC Unused 4 X3 Input 3 4 YB Output 11 X4 1 24V 24V DC YC 1 24V 24V DC 2 NC Unused 2 NC Unu...

Страница 5: ...t from the DIN rail A C B DIN RAIL MOUNTING RIGHT ANGLE Mounting A Insert the longer DIN rail mounter slider until it clicks twice as shown below A B Set the upper hook at the rear side of the unit on the DIN rail C Push in the lower B C Note leave at least 10 mm 39 in at the both side of the unit Dismounting A Push down the DIN rail mounter slider with tip of a mi nus screwdriver B Pull the lower...

Страница 6: ...p CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal Detection Circuit DA DG DB SLD FE SNSR EXC SNSR EXC FE1 PWR PWR 1 2 4 5 3 SNSR EXC SNSR EXC FE1 PWR PWR 1 2 4 5 3 X0 GND NC GND NC 24V Input X0 1 2 4 3 Detection Circuit X7 24V 1 2 4 3 1 2 4 3 1 2 4 3 GND NC Xn 24V 1 2 4 3 Detection Circuit Input...

Страница 7: ...unit mm inch 125 4 92 2 M4 DATA ALLOCATION F 0 1F F 0 1F RX n 0 7 RX n 0 0 Unused RY n 0 F RY n 0 8 Unused Interval timed Response X Refresh Data Y I O DATA DESCRIPTIONS DISCRETE I O 0 15 Input 0 Input 1 Input 2 Input 3 Input 7 Unused Unused 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 15 Unused Unused Unused Unused Unused Output 8 Output 15 0 OFF 1 ON 0 OFF 1 ON ...

Страница 8: ... 6 6659 8510 E mail info m system co jp EM 7767 G P 8 8 COMMUNICATION CABLE WIRING DA DB DG SLD FG DA DB DG SLD FE R7F4DC DA DB DG SLD FE R7F4DC 1 Master module Terminating Resistor blue white yellow 1 Turn on the terminator DIP switch to activate the internal terminating resistor MASTER CONNECTION ...

Отзывы: