background image

R7F4DC-DA16B-C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7767-E  P. 7 / 7

MOUNTING REQUIREMENTS  

unit: mm [inch]

125 [4.92]

2-M4

DATA ALLOCATION

F

0

1F

F

0

1F

RX (n+0) F - RX (n+0) 0

Unused

Unused

Interval timed Response (X)

Refresh Data (Y)

I/O DATA DESCRIPTIONS

 DISCRETE INPUT

0

15

Input 0
Input 1
Input 2
Input 3

Input 15

0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON

0: OFF / 1: ON

COMMUNICATION CABLE WIRING

DA
DB

DG

SLD

FG

DA
DB

DG

SLD

FE

R7F4DC

DA
DB

DG

SLD

FE

R7F4DC

*

1

Master module

Terminating 

Resistor

blue

white

yellow

*

1. Turn on the terminator DIP switch to activate the internal terminating resistor.

 MASTER CONNECTION

Содержание R7F4DC-DA16B-C

Страница 1: ...power source input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24...

Страница 2: ...Green ON when the module is transmitting RD Green ON when the module is receiving 1 Run LED turns off when no command is received from the master device DISCRETE INPUT STATUS INDICATOR LED Green LED...

Страница 3: ...t from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed or power...

Страница 4: ...75 10GY 0 75mm2 Phoenix contact AI1 10 1 0mm2 Phoenix contact AI1 5 10 1 5mm2 Phoenix contact PIN NO ID FUNCTION PIN NO ID FUNCTION X0 1 X0 Input 0 X8 1 X8 Input 8 2 24V 24V DC 2 24V 24V DC 3 GND 0V 3...

Страница 5: ...from the DIN rail A C B DIN RAIL MOUNTING RIGHT ANGLE Mounting A Insert the longer DIN rail mounter slider until it clicks twice as shown below A B Set the upper hook at the rear side of the unit on t...

Страница 6: ...35mm wide 4 16 2 4 3 17 dia 4 16 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal Detection...

Страница 7: ...n 0 0 Unused Unused Interval timed Response X Refresh Data Y I O DATA DESCRIPTIONS DISCRETE INPUT 0 15 Input 0 Input 1 Input 2 Input 3 Input 15 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON...