M-system R7E-YV2 Скачать руководство пользователя страница 3

R7E-YV2

P. 3 / 6

EM-7807-D Rev.4

EXTERNAL DIMENSIONS

  unit: mm (inch)

2

3

4

1

5

10

7

8

9

6

4

5

6

7

1

2

3

30 (1.18)

[5 (.20)]

7–M3 SCREW

TERMINALS

for POWER

10–M3 SCREW 

TERMINALS

for OUTPUT

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

6 (.24)

6 (.24)

115 (4.53)

65 (2.56)

3

(.12)

5.5 (.22)

50 (1.97)

18.5 (.73)

RJ-45 CONNECTOR

CONNECTION DIAGRAM

Connect the unit as in the diagram below.
Note:  In order to improve EMC performance, bond the FG ter-

minal to ground.

Caution: FG terminal is NOT a protective conductor terminal.

 Output Connection Examples

VHn

VLn

+

COMn

WIDE SPAN

VOLTAGE

VHn

VLn +

COMn

NARROW SPAN

VOLTAGE

7

VH0

8

VL0

2

COM0

3

COM0

OUTPUT 0

9

VH1

10

VL1

4

COM1

5

COM1

OUTPUT 1

7

6

0V

24V DC

3

FG

Modbus/

TCP

RJ-45 

CONNECTOR

EXTENSION CONNECTOR

 

OUTPUT RANGE

• 

Wide span voltage

: -10 – +10V DC, -5 – +5V DC, 

 

0 – 10V DC, 0 – 5V DC, 1 – 5V DC

• 

Narrow span voltage

: -1 – +1V DC, 0 – 1V DC, 

 

-0.5 – +0.5V DC

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque

: 0.5 N·m

 

SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co.,Ltd., Nichifu Co.,Ltd.

6 (.24) max

3.3 (.13) max

mm (inch)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7E-YV2

Страница 1: ...and confirm its operational range as indicated below 24V DC rating 24V 10 approx 115mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and output signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to co...

Страница 2: ... ON ON OFF 0 1V DC ON ON ON OFF 0 5 0 5V DC ON ON ON ON PC Configurator setting Caution SW1 3 is unused Be sure to turn off unused one POWER SUPPLY TERMINAL ASSIGNMENT 4 NC 5 NC 6 24V 1 NC 2 NC 3 FG 7 0V NO ID FUNCTION NOTES 1 NC 2 NC 3 FG FG 4 NC 5 NC 6 24V Power input 24V DC 7 0V Power input 0V OUTPUT TERMINAL ASSIGNMENT 6 NC 7 VH0 8 VL0 1 NC 2 COM0 3 COM0 9 VH1 4 COM1 10 VL1 5 COM1 NO ID FUNCTI...

Страница 3: ...IDE SPAN VOLTAGE VHn VLn COMn NARROW SPAN VOLTAGE 7 VH0 8 VL0 2 COM0 3 COM0 OUTPUT 0 9 VH1 10 VL1 4 COM1 5 COM1 OUTPUT 1 7 6 0V 24V DC 3 FG Modbus TCP RJ 45 CONNECTOR EXTENSION CONNECTOR OUTPUT RANGE Wide span voltage 10 10V DC 5 5V DC 0 10V DC 0 5V DC 1 5V DC Narrow span voltage 1 1V DC 0 1V DC 0 5 0 5V DC WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the ...

Страница 4: ...from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection cannot be established normally due to e g wrong IP address other replies such as timeout will be received CHECK CONNECTION TO THE APPLICATION SOFTWARE Check Poin...

Страница 5: ... bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within the slave read write 17 Report Slave ID X Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Reference 21 Write General Reference 22 Mask Write 4X Register 23 Read Write 4X Register 24 Read FIFO Qu...

Страница 6: ...d I Integer 1500 11500 15 115 F Floating Note DO NOT access addresses other than mentioned above Such access may cause problems such as inadequate operation STATUS Analog input modules models R7E SV4 R7E TS4 R7E RS4 R7E MS4 R7E CT4E can show input status of each channel Analog output modules models R7E YS2 R7E YV2 and discrete I O modules models R7E DA16 R7E DC16A R7E DC16B shows 0 at the same add...

Отзывы: