manualshive.com logo in svg
background image

R7E-DC16A

P. 6 / 6

EM-7807-G Rev.4

MODBUS I/O ASSIGNMENTS

ADDRESS

DATA TYPE

DATA

Coil (0X)

 16

Digital Output (discrete output of the basic module)

17 

– 32

Digital Output (discrete output of the extension module)

Inputs (1X)

 16

Digital Input (discrete input of the basic module)

17 

– 32

Digital Input (discrete input of the extension module)

33 

– 48

Reserved (unused)

49 

– 64

Module Status

65 

– 80

Reserved (unused)

Input Registers (3X)

– 4

I

Analog Input

– 16

----

Reserved (unused)

17 

– 24

F

Analog Input

25 

– 48

----

Reserved (unused)

Holding Registers (4X)

– 2

I

Analog Output

– 16

----

Reserved (unused)

17 

– 20

F

Analog Output

21 

– 48

----

Reserved (unused)

I  : Integer, -1500 – +11500 (-15 – +115%)
F : Floating
Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate operation.

 

STATUS

Analog input modules (models: R7E-SV4, R7E-TS4, R7E-RS4, R7E-MS4, R7E-CT4E) can show input status of each channel.
Analog output modules (models: R7E-YS2, R7E-YV2) and discrete I/O modules (models: R7E-DA16, R7E-DC16A, R7E-
DC16B) shows ‘0’ at the same address.

0

15

Input 0 (Burnout, input range error)
Input 1 (Burnout, input range error)
Input 2 (Burnout, input range error)

Unused

Input 3 (Burnout, input range error)
Input 0 (ADC error)
Input 1 (ADC error)
Input 2 (ADC error)
Input 3 (ADC error)

     :

Unused

Burnout, input range error (≤-15%, ≥+115%)
     0 : Normal     1 : Error
ADC error (no response from ADC)
     0 : Normal     1 : Error

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Отзывы: