background image

R7D-YS2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7802-E  Rev.6  P. 6 / 10

 

STATUS

Bit 0 to 7:  Analog output module shows ‘0’ at the same address.
Bit 8 to 10:  Shows the power supply status.

0

15

Remains “0”
Remains “0”
Remains “0”

Unused

Remains “0”
Remains “0”
Remains “0”
Remains “0”
Remains “0”

     :

     :

     :

Network power supply
Unused

Unused

Extension module external power supply

Power supply
     0 : Normal     1 : Error

TRANSMISSION DATA DESCRIPTIONS

 

BASIC MODULE

Transmitted data (word) depends upon the modules types.

MODEL

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

R7D-YS2x

0

2

 

EXTENSION MODULE

Transmitted data (word) for the extension module is added.

MODEL

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

R7D-EAx

1

0

R7D-ECx

0

1

 

STATUS

Status signal can be included in the transmission data 
when the setting is enabled using the PC Configurator soft-
ware (model: R7CON).  For details, refer to “STATUS in I/O 
DATA DESCRIPTIONS”.

STATUS

OUTPUT DATA

*

1

INPUT DATA

*

2

(R7D to Master)

(Master to R7D)

Enabled

1

0

Disabled

0

0

*1. Output Data means those sent to the master.
*2. Input Data means those received from the master.

WIRING INSTRUCTIONS

 

SCREW TERMINAL (Output)

Torque: 0.5 N·m

• SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

 

EURO TYPE CONNECTOR TERMINAL (DeviceNet)

Applicable wire size: 0.2 – 2.5 mm

2

Stripped length: 7 mm

Содержание R7D-YS2

Страница 1: ...itable for use in Installation Catego ry II and in a Pollution Degree 2 environment Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is to be s...

Страница 2: ...ctory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 125 kbps factory setting 1 250 kbps 2 500 kbps 3 thr 9 Auto tra...

Страница 3: ...software program INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 0 3276 7 sec 1 0 sec Status Data ON Disable OFF Enable OFF Enable Serial ID English one byte charact...

Страница 4: ...NS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 2 3 4 1 5 10 7 8 9 6 2 3 4 1 5 30 1 18 5 20 3 12 3 12 5 5 22 DIN RAIL 35mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 10 M...

Страница 5: ...e 1 Analog Output Module R7D EA16 without Status Analog Output Module Input Data Status Begin 0 Begin 0 CH0 CH1 1 2 Output Data Example 2 Analog Output Module R7D EC16x with Status Analog Output Modul...

Страница 6: ...added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Status signal can be included in the transmission data when the setting is enabled using the PC Config...

Страница 7: ...ng the R7D Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out o...

Страница 8: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Страница 9: ...ment Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions fr...

Страница 10: ...ween cables and noise sources Grounding in pig tail form is not effective Points of cautions applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external...

Отзывы: