R7D-SV4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7802-A Rev.7 P. 2 / 10
COMPONENT IDENTIFICATION
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
MS
X10
X1
NODE ADD.
B.RATE
CNFG.
1
2
3
4
5
6
7
8
10 11 12 13
2
3
4
1
15 16 17 18
7
8
9
6
14
5
NS
2 3 4
1
5
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) DeviceNet, Power Supply Terminals
(G) Input Terminals
(A)
(F)
(G)
(B)
(C)
(D)
(E)
■
STATUS INDICATOR LED
ID
STATE
TO INDICATE
MS
Green
Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red
Critical failure
Blinking Red
Minor failure
OFF
No power supplied
NS
Green
Link on-line and connections in the
established state
Blinking Green Link on-line but no connections in
the established state
Red
Critical link failure
Blinking Red
Minor link failure
OFF
No power supplied
■
NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■
BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking
The R7D communicates in the baud rate setting detected at
the startup with the switch set to the positions 0 (125 kbps),
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network
to determine the baud rate on the network.
■
OPERATING MODE
(*) Factory setting
• Extension: SW1-1, 1-2
SW1-1
SW1-2
EXTENSION
OFF
OFF
No extension (*)
ON
OFF
Discrete input, 8 or 16 points
OFF
ON
Discrete output, 8 or 16 points
• Conversion Rate / Accuracy: SW1-3, 1-4
SW1-3
SW1-4
CONVERSION RATE / ACCURACY
OFF
OFF
80 msec. / ±0.1% (*)
ON
OFF
40 msec. / ±0.2%
OFF
ON
20 msec. / ±0.4%
ON
ON
10 msec. / ±0.8%
• Input Range: SW1-5, 1-6, 1-7, 1-8
SW1-5
SW1-6
SW1-7
SW1-8
INPUT RANGE
OFF
OFF
OFF
OFF
-10 – +10V DC (*)
ON
OFF
OFF
OFF
-5 – +5V DC
OFF
ON
OFF
OFF
-1 – +1V DC
ON
ON
OFF
OFF
0 – 10V DC
OFF
OFF
ON
OFF
0 – 5V DC
ON
OFF
ON
OFF
1 – 5V DC
OFF
ON
ON
OFF
0 – 1V DC
ON
ON
ON
OFF
-0.5 – +0.5V DC
ON
OFF
OFF
ON
-20 – +20mA DC
OFF
ON
OFF
ON
4 – 20mA DC
ON
ON
OFF
ON
0 – 20mA DC
ON
ON
ON
ON
PC Configurator setting
■
DeviceNet TERMINAL ASSIGNMENT
2
3
4
1
5
NO.
ID
FUNCTION, NOTES
1
V+
Network power
2
CAN_H
Network data High
3
Drain
Shield
4
CAN_L
Network data Low
5
V–
Network power supply –
■
INPUT TERMINAL ASSIGNMENT
10
VL0
11
I0
12
VL1
1
VH0
2
COM0
3
VH1
13
I1
4
COM1
14
NC
5
NC
15
VL2
6
VH2
16
I2
7
COM2
17
VL3
8
VH3
9
COM3
18
I3
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
VH0 Wide span volt. 0 10
VL0 Narrow span volt. 0
2 COM0 Common 0
11
I0
Current range 0
3
VH1 Wide span volt. 1 12
VL1 Narrow span volt. 1
4 COM1 Common 1
13
I1
Current range 1
5
NC
No connection
14
NC
No connection
6
VH2 Wide span volt. 2 15
VL2 Narrow span volt. 2
7 COM2 Common 2
16
I2
Current range 2
8
VH3 Wide span volt. 3 17
VL3 Narrow span volt. 3
9 COM3 Common 3
18
I3
Current range 3