R7C-YS4
EM-7801-AE P. 2 / 9
COMPONENT IDENTIFICATION
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
ERR
RD
RUN
SD
PWR
X10
X1
STATION ADD.
B.RATE
CNFG.
1 2 3 4 5 6 7 8
4
5
6
7
1
2
3
2
3
4
1
5
10
7
8
9
6
(A) Status Indicator LED
*
1
(B) Station Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) CC-Link, Power Supply Terminals
(G) Output Terminals
(H) Terminating Resistor SW
*
1. Refer to ‘Status Indicator LED’ section for detailed information.
(A)
(F)
(G)
(B)
(C)
(D)
(E)
TERM
ON
OFF
■
SIDE VIEW
■
FRONT VIEW
(H)
■
STATUS INDICATOR LED
ID
COLOR FUNCTION
PWR
Red
Turns on when the internal 5V is sup-
plied normally.
RUN
Red
Turns on when the refresh data is re-
ceived normally.
ERR
Red
Turns on when the received data is
abnormal.
SD
Red
Turns on when the module is transmit-
ting.
RD
Red
Turns on when the module is receiving.
■
STATION ADDRESS
Station Address is selected between 1 and 64 in decimal.
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Station Address Setting (x1)
Station Address Setting (x10)
■
BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
■
OPERATING MODE
(*) Factory setting
• Output at the loss of communication (SW1-4)
SW1-4
OUTPUT AT THE LOSS OF COMMUNICATION
OFF
Reset the output (to -15%)
ON
Hold the output (*)
(maintains the last data received normally)
Note : Be sure to set unused SW1-1 through 1-3 and 1-5
through 1-8 to OFF.
■
POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT
4
DA
5
DG
6
U(+)
1
DB
2
SLD
3
FG
7
V(–)
NO.
ID
FUNCTION, NOTES
1
DB
White
2
SLD
Shield
3
FG
FG
4
DA
Blue
5
DG
Yellow
6
U(+)
Power input
7
V(–)
Power input
■
OUTPUT TERMINAL ASSIGNMENT
6
NC
7
I0
8
I1
1
NC
2
COM0
3
COM1
9
I2
4
COM2
10
I3
5
COM3
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
NC
No connection
6
NC
No connection
2 COM0 Common 0
7
I0
Current output 0
3 COM1 Common 1
8
I1
Current output 1
4 COM2 Common 2
9
I2
Current output 2
5 COM3 Common 3
10
I3
Current output 3
■
TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)