R7C-TS4

EM-7801-B  Rev.10  P. 3 / 10

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

INDICATOR LED

 

STATUS INDICATOR LED

PWR

RUN

ERR

SD 

*

1

RD

STATUS 

*

2

ON

ON

BL

BL

ON

Communicates normally with occasional CRC errors due to noise interference.

ON

ON

BL

BL

ON

Communicates normally but the Baud Rate and/or Station Address switches failed.  
ERR LED blinks approximately in 0.5 seconds intervals.

ON

ON

BL

BL

OFF ----

ON

ON

BL

OFF

ON

CRC error found in the received data.  Unable to respond.

ON

ON

BL

OFF

OFF ----

ON

ON

OFF

BL

ON

Normal communication

ON

ON

OFF

BL

OFF ----

ON

ON

OFF

OFF

ON

Unable to receive data addressed to the station.

ON

ON

OFF

OFF

OFF ----

ON

OFF

BL

BL

ON

Performs the interval-timed responses but CRC error found in receiving the refresh 
data.

ON

OFF

BL

BL

OFF ----

ON

OFF

BL

OFF

ON

CRC error found in the data addressed to the station.

ON

OFF

BL

OFF

OFF ----

ON

OFF

OFF

BL

ON

Link is not started.

ON

OFF

OFF

BL

OFF ----

ON

OFF

OFF

OFF

ON

No data addressed to the station.  Or unable to receive data addressed to the station 
due to noise interference.  (Missing parts of the data sent from the master)

ON

OFF

OFF

OFF

OFF Unable to receive data due to wire breakdown

ON

OFF

ON

OFF ON/OFF Faulty Baud Rate and/or Station Address setting

OFF

OFF

OFF

OFF

OFF Power input removed.  Or power supply failure.

OFF = OFF, ON = ON, BL = Blinking
*1. SD LED may look not blinking but ON with high baud rate and fewer connected modules.
*2. LEDs indicated with “----” in STATUS rarely occurs in normal operation (LED failure or the like as possible cause).

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R7CON for detailed operation.

 

INTERFACE MODULE SETTING 

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Communication Timeout

0.0 – 3276.7 (sec.)

1.0 (sec.) 

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

TC Type

K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S

C (WRe 5-26)
N
U
L
P (Platinel II)
 (PR) 

K (CA) 

Temp Unit

C, F, K

C

Zero scale

-32000 to +32000

0

Full scale

-32000 to +32000

10000

Bias

-320.00 to +320.00

0.00

Gain

-3.2000 to +3.2000

1.0000

Zero temp

Depends on sensor type

0.00 (degC) 

Full temp

Depends on sensor type

0.00 (degC) 

 

EXTENSION MODULE SETTING

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Output Hold/Clear

Output Hold
Output Clear

Output Hold

Содержание R7C-TS4

Страница 1: ...be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of th...

Страница 2: ...switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Di...

Страница 3: ...o noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting...

Страница 4: ...4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 Input Connection Example INn INn CJn CJn T C CJC SENSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG...

Страница 5: ...ocated other than at the extreme ends of communication line DATA ALLOCATION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval t...

Страница 6: ...Burnout input range error Unused Input 3 Burnout input range error Input 0 ADC error Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Burnout input range error 15 115 0 Normal 1 Error ADC...

Страница 7: ...dequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choos...

Страница 8: ...tically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impe...

Страница 9: ...y be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise ove...

Страница 10: ...nts of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cov...

Отзывы: