CONFORMITY WITH CE MARKING

 

CE MARKING

CE marking requires to integrate safety regulations existed in each country in EU territory and to secure smooth distribution 
of products of which safety is guaranteed.  It is mandatory by law that products distributed and sold in EU territory to have 
CE mark which shows that the product conforms with the requirements of EU Directive.  Each EU Directive describes the 
scope of apparatuses to which that EU Directive is applied.  M-System’s R7C must conform with EMC Directive.
Each Directive states only basic requirements.  In order to mark the CE on an assembled machinery equipment, its manufac-
turer needs to check the overall conformity with Directives applicable to it.

 

WARNINGS AND CAUTIONS WHEN INSTALLING THE R7C

The R7C needs to be installed in a control panel.  This is effective not only to ensure general safety but also to contain noise 
emissions by the R7C inside the control panel.  We conduct a series of testing to see that the product conforms to EMC Direc-
tive while it is installed in the control panel.
Warning and cautions when installing R7C are stated below.

• Use control panels with an internal panel plate, both made of metal, when installing the R7C.
• Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped-

ance at high frequency.

• Use shielded cables for the signals taken out of the control panel.
• Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel.

    Note: If electromagnetic radiation disturbance increases by grounding the FG terminal, remove the grounding.

• When painting the internal plate of the control panel, apply masking to expose metal surface to secure conductivity at the 

sections where the following parts are attached:

  - Bolts attaching the internal panel to the control panel
  - Ground for the FG of the R7C module
  - Earth clamp on the shielded cable

• Noise emissions inside the control panel might leak through its openings.  Design them as small as possible.  Recommended 

diameter is 10 cm or less.

Supplement:

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Prevent noise leakage by wrapping cables using shield covers, shield tubes and flexible conduits etc. if noise leaks through 

the cable outlet.

• Use an electromagnetic shield gasket and block up the gap between the control panel cabinet and its cover, if noise leaks 

through it.

• Connecting the internal panel plate and the cover of the control panel to the main cabinet using an earth strap may be 

effective to strengthen the grounding.

• Electromagnetically shielded control panel cabinet is effective for shielding.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-DC8C

Страница 1: ...ay invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL ...

Страница 2: ...ddress 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Station Address Setting x1 Station Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at the loss of communication SW1 4 SW1 4 OUTPUT AT THE LOSS OF COMMUNICATION OFF Reset the output turned off ON Hol...

Страница 3: ...N OFF BL OFF ON CRC error found in the data addressed to the station ON OFF BL OFF OFF ON OFF OFF BL ON Link is not started ON OFF OFF BL OFF ON OFF OFF OFF ON No data addressed to the station Or unable to receive data addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OF...

Страница 4: ... 3 4 1 2 5 3 FG 6 7 24V DC 0V SLD DG DB DA 10 1 0V 24V Output Connection Example In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal 4 Points common 10 14 1 2 5 11 24V Y0 0V Y3 COM0 COM0 18 6 9 15 Y4 Y7 COM1 COM1 8 Points common 10 14 1 2 5 11 24V 24V DC Y0 0V Y3 15 Y4 18 Y7 COM0 COM0 6 9 COM1 COM1 24V DC 5 2 6 4 7 13 8 9 14...

Страница 5: ...ATA ALLOCATION RY n 0 7 to RY n 0 0 Unused R7C DC8C 0 F 1F Interval timed Response X Unused 0 F 1F Refresh Data Y R7C DC8C I O DATA DESCRIPTIONS 0 15 Output 0 Output 1 Output 2 8 points Output 3 Output 7 Not Used Remains 0 0 OFF 1 ON DISCRETE OUTPUT WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongu...

Страница 6: ... a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the con...

Страница 7: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7C Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Страница 8: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the im...

Страница 9: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic ...

Отзывы: