R7C-CT4E

EM-7801-R  Rev.2  P. 7 / 10

CONFORMITY WITH CE MARKING

 

CE MARKING

CE marking requires to integrate safety regulations existed in each country in EU territory and to secure smooth distribution 
of products of which safety is guaranteed.  It is mandatory by law that products distributed and sold in EU territory to have 
CE mark which shows that the product conforms with the requirements of EU Directive.  Each EU Directive describes the 
scope of apparatuses to which that EU Directive is applied.  M-System’s R7C must conform with EMC Directive.
Each Directive states only basic requirements.  In order to mark the CE on an assembled machinery equipment, its manufac-
turer needs to check the overall conformity with Directives applicable to it.

 

WARNINGS AND CAUTIONS WHEN INSTALLING THE R7C

The R7C needs to be installed in a control panel.  This is effective not only to ensure general safety but also to contain noise 
emissions by the R7C inside the control panel.  We conduct a series of testing to see that the product conforms to EMC Direc-
tive while it is installed in the control panel.
Warning and cautions when installing R7C are stated below.

• Use control panels with an internal panel plate, both made of metal, when installing the R7C.
• Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped-

ance at high frequency.

• Use shielded cables for the signals taken out of the control panel.
• Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel.

    Note: If electromagnetic radiation disturbance increases by grounding the FG terminal, remove the grounding.

• When painting the internal plate of the control panel, apply masking to expose metal surface to secure conductivity at the 

sections where the following parts are attached:

  - Bolts attaching the internal panel to the control panel
  - Ground for the FG of the R7C module
  - Earth clamp on the shielded cable

• Noise emissions inside the control panel might leak through its openings.  Design them as small as possible.  Recommended 

diameter is 10 cm or less.

Supplement:

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Prevent noise leakage by wrapping cables using shield covers, shield tubes and flexible conduits etc. if noise leaks through 

the cable outlet.

• Use an electromagnetic shield gasket and block up the gap between the control panel cabinet and its cover, if noise leaks 

through it.

• Connecting the internal panel plate and the cover of the control panel to the main cabinet using an earth strap may be 

effective to strengthen the grounding.

• Electromagnetically shielded control panel cabinet is effective for shielding.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-CT4E

Страница 1: ...o remote locations Choose a surge protector with its maximum surge voltage 40V or less between lines Rec ommended M System model MDP D24 POWER INPUT RATING OPERATIONAL RANG Locate the power input rati...

Страница 2: ...5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discrete output 8 or 16 points Conv...

Страница 3: ...OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF OFF Power input removed Or power supply failure OFF OF...

Страница 4: ...ERMINALS for CC Link POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 0V 24V DC FG SLD DG DB DA 10 K0 11 L0 INPUT 0 K1 L1 INPUT 1 K2 L2 INPUT 2 K3 L3 INPUT 3 12 13 15 1...

Страница 5: ...TION Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval timed Response X Refresh Data Y RX n 0 F to RX n 0 0 Reserved Status RX...

Страница 6: ...Input 1 ADC error Input 2 ADC error Input 3 ADC error Unused Input range error 15 115 0 Normal 1 Error ADC error no response from ADC 0 Normal 1 Error STATUS Analog input module without extension mod...

Страница 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C modul...

Страница 8: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 9: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to...

Страница 10: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To con...

Отзывы: