R30NE1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-9019 Rev.1 P. 5 / 10
CHECKING ETHERNET CONNECTION
■
IP ADDRESS SETTING
R30NE1 does not support BootP Table Software.
Use PC Configurator Software (model: R30CFG) to set the IP Address.
The Modbus/TCP Port No. is fixed at 502.
■
WIRING
Connect an Ethernet cable to the RJ-45 port of your PC.
■
STATUS INDICATOR LEDs
Confirm that the LINK LED is turned on if the wiring is correct.
Specifically, the LINK10 LED is ON when the unit is connected at 10 Mbps while the LINK100 LED is ON when connected
at 100 Mbps.
■
CHECKING CONNECTION OF R30NE1
Enter the following “ping command” in the Command Prompt on Windows OS.
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
If the R30NE1 is successfully connected, you will receive a response as follows.
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Ping statistics for ***.***.***.***
Packets:Sent=4,Received=4,Lost=0(0% loss)
In case of connection failure due to wrong IP address or the like, replies indicating, for example, ‘timeout’ will be received.
■
CHECKING CONNECTION TO THE APPLICATION SOFTWARE
Check Point 1: LINK LEDs
When connection is established normally, the LINK10 or LINK100 LED is turned on regardless of whether or not data com-
munication is in progress.
Check power supply to the hub, etc. if neither LED is turned on.
Check Point 2: RUN Indicator LED
Confirm that the RUN Indicator LED turns green in normal data communication with the application software.