background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9019  Rev.1  P. 1 / 10

INSTRUCTION MANUAL

MODBUS/TCP INTERFACE MODULE

MODEL

R30NE1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Network module ..................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This unit must be mounted inside the instrument panel 

of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

HOT SWAPPABLE MODULES

• It is possible to replace a module with the power supplied 

provided that the module is replaced with one with the 
same model number and installed in the same base slot.

• Be sure to replace a module when it is not communicating 

with the host as it may affect the system.  Note that re-
placing multiple modules at one time may greatly change 
line voltage levels.  We strongly recommend to replace 
them one by one.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 10 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

Содержание R30NE1

Страница 1: ...panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity HOT SWAPPABLE MODULES It is possible t...

Страница 2: ...IEW BOTTOM VIEW SIDE VIEW Specifications Lock Tab Base Fixing Screw Positioning Guide STATUS INDICATOR LED ID FUNCTION COLOR STATUS PWR Main Unit Internal Power Green OFF Error Power off ON Normal RUN...

Страница 3: ...age the positioning guide of the module with the In stallation Base 2 Pivot the module on the positioning guide and press it down until the lock tab clicks into place Positioning guide 3 Tighten the b...

Страница 4: ...TCP Ethernet INTERNAL POWER PC CONFIGURATOR SETTING The following parameter items can be set with using PC Configurator Software model R30CFG Refer to the users manual for the R30CFG for detailed oper...

Страница 5: ...n Windows OS C WINDOWS ping Enter IP address in decimal If the R30NE1 is successfully connected you will receive a response as follows ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 R...

Страница 6: ...m Event Log X A status word an event counter a message count and a field of event bytes 13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave read write 16 P...

Страница 7: ...ction of the unit 1 Module Status indicates whether or not an I O module is mounted on each slot The bit corresponding to the mounted slot turns to 1 and the unmounted slot to 0 2 Error Status indicat...

Страница 8: ...4 When there is a blank slot data of the latter slot number is transmitted to the host PC PLC so that no blank data is trans mitted The table below shows an example of I O configuration and the figure...

Страница 9: ...it binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data...

Страница 10: ...0 ANALOG DATA 32 bit data models R3 BA32A BC32A etc 32 bit binary data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0...

Отзывы: