MODEL: R30NCIE1
R30NCIE1 SPECIFICATIONS
ES-9020 Rev.6 Page 1/7
https://www.m-system.co.jp/
Remote I/O R30 Series
NETWORK MODULE
(CC-Link IE Field network)
Functions & Features
• Interchanges analog or discrete I/O signals with the
filedbus (CC-Link IE Field network)
• Combined with R3 Series I/O modules
98 [3.86]
110
[4.33]
25
[.98]
mm [inch]
MODEL: R30NCIE1[1]
ORDERING INFORMATION
• Code number: R30NCIE1[1]
Specify a code from below for [1].
(e.g. R30NCIE1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
CAUTION
• The internal bus communication period for R3 series I/O
modules installed on the R30EBS is as follows.
Internal bus communication period = 6 msec. × number of
I/O 10 msec. (Data update period of main CPU)
Example: Four R3 I/O modules
6 msec. × 4 + 10 msec. = 34 msec.
Even when the R30EBS is mounted to the R30BS, the
internal bus communication period of R30 series is kept to
approx. 1 msec.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
Downloadable at M-System’s web site.
For connecting to PC, use commercially available Mini-B
type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2 and R3S-CM2A)
GENERAL SPECIFICATIONS
Connection
CC-Link IE Field: RJ-45 connector
Internal bus: Via the Installation Base (model: R30BS)
Internal power: Via the Installation Base (model: R30BS)
Isolation: CC-Link IE Field to internal bus or internal power
Input type & range:
R30 series I/O module: PC configuration software (model:
R30CFG)
R3 series I/O module: PC configuration software (model:
R3CON)
Network address: PC configuration software (model:
R30CFG)
Internal bus communication cycle: Approx. 1 msec.
Status indicator: RUN, RD, SD, D LINK, ERR, L ER, LINK
(Refer to the instruction manual.)
CC-Link IE Field COMMUNICATION
Protocol: IEEE 802.3
Transmission type: 1000BASE-T
Communication speed: 1 Gbps
Network cable: Cable conformed to CC-Link IE Field
Double shielded twist pair cable (CAT5e)
RJ-45 connector
Network topology: Line, star and ring
Max. number stations: 120 (Total slave station)
(Number of max. connectable slaves may vary depending
on the master module. Refer to the instruction manual of
the master module)
Max. station-to-station distance: 100 m
Station type: Remote device station
Link device: RX/RY 128 points, RWw/RWr 64 points