MODEL: R30NCIE1

R30NCIE1 SPECIFICATIONS

ES-9020 Rev.6   Page 5/7

https://www.m-system.co.jp/

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

0

15

Module 1

Module 2

Module 3
      :

Module 16

Shows each module's availability and error status.

I/O DATA DESCRIPTIONS

■OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES
When the communication between the network module and the I/O modules is lost due to an error in an input module, the last
process values are held until the communication is re-established.

■ ANALOG DATA (16-bit data, models: R30SV4, R30SV2, R30YV4, R30YS4, R30US4, etc.)

0

15

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). 
Negative percentage is represented in 2's complements.

■ ANALOG DATA (16-bit data, models: R30RS4, R30TS4, R30US4, etc.)

0

15

16-bit binary data.
With °C  temperature unit, raw data is multiplied by 10.  For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.
For example, 135.4°F is converted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

■ ANALOG DATA (16-bit data, models: R30CT4E etc.)

0

15

16-bit binary data.
Integer obtained by multiplying unit value (A) by 100.
In case of CLSE-R5, integer obtained by multiplying unit value (A) by 1000. 

■ ANALOG DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)

0

15

+0

0

15

Higher 16 bits

+1

32-bit binary data is used for accumulated counts, encoder positions and active energy.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.

Lower 16 bits

Содержание R30NCIE1

Страница 1: ...re model R30CFG PC configurator software model R3CON Downloadable at M System s web site For connecting to PC use commercially available Mini B type USB cable provided by user R3 series I O modules ex...

Страница 2: ...30BS Weight 125 g 0 28 lb PERFORMANCE Insulation resistance 100 M with 500 V DC Dielectric strength 1500 V AC 1 minute CC Link IE Field to internal bus or internal power 1500 V AC 1 minute power input...

Страница 3: ...R30YN16A 1 R30EBS04 1 R3 SV8 8 2 R3 YV8 8 3 R3 DA32A 2 4 R3 DC32A 2 0 15 RWr n 0 Slot 1 2 4 6 8 10 12 14 Slot 2 Slot 3 Slot 4 INPUT DATA The figure below shows the data sent from the device to the mas...

Страница 4: ...tus for each module of R3 series The bit corresponding to such module turns to 1 as described below When the each module is detached the error bit is held R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A i...

Страница 5: ...is represented in 2 s complements ANALOG DATA 16 bit data models R30RS4 R30TS4 R30US4 etc 0 15 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted i...

Страница 6: ...y data is used for BCD Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits 16 POINT DISCRETE DATA models R30XN16A R30YN...

Страница 7: ...ing CN1 and CN2 of RJ 45 connector for CC Link IE Field network there is no restriction for connection order INTERNAL BUS INTERNAL POWER RJ 45 MODULAR JACK RJ 45 MODULAR JACK USB CONNECTOR PC CONFIGUR...

Отзывы: