COMPONENT IDENTIFICATION
■
FRONT VIEW
RUN LED
ERR LED
1
2
3
4
5
6
7
8
9
10
■
SIDE VIEW
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
■
SIDE DIP SW
(*) Factory setting
Be sure to turn off the power supply to the module when-
changing settings. Reset the count after setting changes.
•
SW1, SW2
Count Reset Enable : Back to 0 at overflow
Disable : Halt at 999 999 999
Power Factor may start hunting around 1.
SW
FUNCTION
0 : OFF(
*
)
1 : ON
SW1-2
active energy count reset
disable
enable
SW1-3
active energy
bidirectional current
disable
enable*
1
SW1-6
active energy count reset
disable
enable
SW1-7
active energy
bidirectional current
disable
enable*
1
SW2-1 power factor LEAD polarity
normal
inverted
*1. Both active energy count reset and reactive energycount re-
set are fixed at ‘disable.’
The count stops at ±999 999 999.
When the bidirectional current computation is enabled,the
outgoing active energy and the LEAD reactive energy be-
come 0.
Power Factor Polarity
0
-1.0
1.0
COS
q
DEG
90
-90
-180
(LEAD)
180
(LAG)
Inverted
Normal
•
SW3
The maximum available active energy count is 10
9
.
SW
0 : OFF(
*
)
1 : ON
SW3-1
----
count reset
How to Reset
Set the SW3-1 to ON and turn on the power supply. Wait
until the RUN LED (red) starts flashing and the ERR LED
(green) turns on. Then turn the power supply off and reset
the SW3-1 to OFF.
Turn all switches off other than the above.
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the input abnormality;
Green in normal operating conditions.