R3-SV8B
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8414 Rev.5 P. 2 / 3
COMPONENT IDENTIFICATION
SW2
SW1
ON
1
2
3
4
5
6
7
8
ON
ON
1
2
3
4
5
6
7
8
SW3
1
2
3
4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
■
FRONT VIEW
ERR LED
RUN LED
■
SIDE VIEW
Range
Input 1-4 (SW1)
or
Input 5-8 (SW2)
Conv.
Rate
Functions
■
SIDE DIP SW
(*) Factory setting
• Input Range: SW1, SW2
(selectable per 4 channels)
INPUT 1 through INPUT 4 (SW1)
RANGE
INPUT 5 through INPUT 8 (SW2)
1
2
3
4
OFF
OFF
OFF
OFF
-30 – +30V (*)
ON
OFF
OFF
OFF
-15 – +15V
OFF
ON
OFF
OFF
0 – 30V
ON
ON
OFF
OFF
0 – 15V
• Conversion Rate: SW3-1, 3-2
SW
CONVERSION RATE
160 ms (
*
)
80 ms
40 ms
20 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
Note: Be sure to set unused SW1-5 through 1-8, SW2-5
through 2-8, SW3-3 and 3-4 to OFF.
■
STATUS INDICATOR LED
RUN indicator:
Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator:
Bi-color (red/green) LED;
Red with input circuit abnormality (AD con-
verter response failure);
Green in normal operating conditions.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Zero Scale
-32000 to +32000
0
Full Scale
-32000 to +32000
10000
Zero Adjust
-320.00 to +320.00
0.00
Full Adjust
-32000 to +32000
1.0000
Unused
0: Enable
1: Disable
0: Enable