R3-SV4
P. 2 / 3
EM-8366 Rev.3
COMPONENT IDENTIFICATION
•
Conversion Rate
: SW3
SW
CONVERSION RATE
80 ms (
*
)
40 ms
20 ms
10 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
(*) Factory setting
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
■
FRONT VIEW
■
SIDE VIEW
ERR LED
RUN LED
Conv.
Rate
Input 2 (SW1)
or
Input 4 (SW2)
Range
Input 1 (SW1)
or
Input 3 (SW2)
■
SIDE DIP SW
•
Input Range
: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
INPUT 3 (SW2)
INPUT 4 (SW2)
RANGE
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF -10 – +10V (*)
ON OFF OFF OFF ON OFF OFF OFF -5 – +5V
OFF ON OFF OFF OFF ON OFF OFF -1 – +1V
ON
ON OFF OFF ON
ON OFF OFF 0 – 10V
OFF OFF ON OFF OFF OFF ON OFF 0 – 5V
ON OFF ON OFF ON OFF ON OFF 1 – 5V
OFF ON
ON OFF OFF ON
ON OFF 0 – 1V
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the input circuit abnormality (AD
converter response failure);
Green in normal operating conditions.