R3-RS8B
P. 2 / 3
EM-8341
COMPONENT IDENTIFICATION
n
SIDE DIP SW
•
RTD Type
: SW1, SW2 (selectable per 4 channels)
SW2
SW1
ON
1
2
3
4
5
6
7
8
ON
ON
1
2
3
4
5
6
7
8
SW3
1
2
3
4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
FRONT VIEW
ERR LED
RUN LED
SIDE VIEW
Input 1-4 (SW1)
or
Input 5-8 (SW2)
RTD
Conv.Rate
Temp. Unit
Burnout
n
n
INPUT 1 through INPUT 4 (SW1)
INPUT 5 through INPUT 8 (SW2)
RTD
1 2 3 4
OFF
OFF
OFF
OFF
Pt 100 (*)
(JIS ’97, IEC)
ON
OFF
OFF
OFF
Pt 100
(JIS ’89)
OFF
ON
OFF
OFF
JPt 100
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
n
DIMENSIONS mm (inch)
TERMINAL
COVER
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
28–M3
SCREW
6.2
(.24)
n
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with burnout;
Green in normal operating conditions.
•
Burnout
: SW3
•
Temperature Unit
: SW3
•
Conversion Rate
: SW3
SW3-1
BURNOUT
OFF
Upscale (*)
ON Downscale
SW3-2
TEMP. UNIT
OFF
°C (*)
ON
°F
SW
CONV. RATE
160
80
40
20
SW3-3
OFF(*)
ON
OFF
ON
SW3-4
OFF(*)
OFF
ON
ON
(*) Factory setting