POWER SUPPLY MODULE

MODEL

R3-PS3

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Power supply module ................................................... (1)

 MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 CONFORMITY WITH EU DIRECTIVES

• This  equipment  is  suitable  for  use  in  Installation  Cat

-

egory II and Polution Degree 2.  Reinforced insulation 
(internal power to power input to: 300 V) and basic insu-
lation (internal power to RUN contact output: 300 V) are 
maintained.  Prior to installation, check that the insula-
tion class of this unit satisfies the system requirements.

• Altitude up to 2000 meters
• The  equipment  must  be  mounted  inside  the  instrument 

panel of a metal enclosure.

• The  equipment  must  be  installed  such  that  appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel 

configurations,connected devices, connected wires, may 
affect the protection level of this unit when it is integrated 
in a panel system. The user may have to review the CE re-
quirements in regard to the whole system and employ ad-
ditional protective measures to ensure the CE conformity.

 POWER INPUT RATING & OPERATIONAL RANGE

 Locate the power input rating marked on the product and con-

firm its operational range as indicated below:

  85 – 132 V AC rating: 85 – 132 V, 47 – 66 Hz, approx. 100 VA 

100 – 120 V AC rating: 85 – 132 V, 47 – 66 Hz, approx. 100 VA 
170 – 264 V AC rating: 170 – 264 V, 47 – 66 Hz, approx. 100 VA 
200 – 270 V AC rating: 170 – 264 V, 47 – 66 Hz, approx. 100 VA 
24 V DC rating: 24 V ±10%, approx. 50 W or 2.0 A at 24 V

  110 V DC rating: 85 – 150 V, approx. 50 W or 440 mA at 110 V

 GENERAL PRECAUTIONS

• Before you remove the unit from its base or mount it, turn 

off the power supply for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C     

(14 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  close  to  noise  sources  (relay  drive 

cable, high frequency line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup

-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).
For heat dissipation, install the power supply module into 
the rightmost slot or leftmost slot. For redundant power 
system, install two modules in series into the rightmost slot 
or leftmost slot. If there is no problem, the rightmost slot is 
recommended.  
In case of redundant power system use, be sure to install 
two same current capacity power supply modules (model: 
R3-PS3) in series.  The combination of different current ca-
pacity power supply module or interface module with power 
supply is not available.  