COMPONENT IDENTIFICATION

1

11
12
13
14
15
16
17
18
19
20

2
3
4
5
6
7
8
9

10

ON

8

7

6

5

4

3

2

1

SW1

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

FRONT VIEW

SIDE VIEW

ERR LED

RUN LED

Start

Count

Unused

Alarm 2

Alarm 1

Count

Mode

Unused

Input

Range

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Green LED turns on in normal operating 

conditions.

 

SIDE DIP SW

(*) Factory setting

• Input Range: SW1-1 through 1-3, SW2-1 through 2-3

INPUT 1 (SW1)

INPUT RANGE

INPUT 2 (SW2)

1

2

3

OFF

OFF

OFF

0 – 100 kHz (*)

ON

OFF

OFF

0 – 10 kHz

OFF

ON

OFF

0 – 1 kHz

ON

ON

OFF

0 – 100 Hz

OFF

OFF

ON

0 – 10 Hz

ON

OFF

ON

0 – 1 Hz

OFF

ON

ON

0 – 0.1 Hz

• Count Mode: SW1-4, 1-5, SW2-4, 2-5

INPUT 1 (SW1)

COUNT MODE

INPUT 2 (SW2)
4

5

OFF

OFF

Mode 0 : 1 count / pulse (*)

ON

OFF

Mode 1 : 1 count / pulse

OFF

ON

Mode 2 : 2 counts / pulse

ON

ON

Mode 3 : 4 counts / pulse

• Alarm Contact Form: SW1-6, 1-7, SW2-6, 2-7

INPUT 1 (SW1)

ALARM CONTACT FORM

INPUT 2 (SW2)

ALARM 1

ALARM 2

6

7

OFF

OFF

ON (short) at alarm (*)

ON

OFF

OFF (open) at alarm

• Start Count: SW3-1

SW

START COUNT AT POWER ON

0

*

1

 count (

*

)

Stored count

SW3-1

OFF

ON

*1.  Start (Reset) count can be modified using the R3CON PC 

Configurator software.

Note:  Be sure to set unused SW1-8, SW2-8 and SW3-2 through 

3-4 to OFF.

Содержание R3-PA2

Страница 1: ...m ity HOT SWAPPABLE MODULES Replacing the module does not affect other modules on the same base Thus the module can be replaced while the power is ON However replacing multiple modules at once may greatly change live voltage levels We highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for main...

Страница 2: ...tions SIDE DIP SW Factory setting Input Range SW1 1 through 1 3 SW2 1 through 2 3 INPUT 1 SW1 INPUT RANGE INPUT 2 SW2 1 2 3 OFF OFF OFF 0 100 kHz ON OFF OFF 0 10 kHz OFF ON OFF 0 1 kHz ON ON OFF 0 100 Hz OFF OFF ON 0 10 Hz ON OFF ON 0 1 Hz OFF ON ON 0 0 1 Hz Count Mode SW1 4 1 5 SW2 4 2 5 INPUT 1 SW1 COUNT MODE INPUT 2 SW2 4 5 OFF OFF Mode 0 1 count pulse ON OFF Mode 1 1 count pulse OFF ON Mode 2 ...

Страница 3: ... 1 Speed High 2 Speed Low 3 Position High 4 Position Low Alarm 1 1 Speed High Alarm 2 2 Speed Low Alarm level Speed 0 00 to 100 00 Position 100 000 000 to 100 000 000 Alarm 1 Speed 80 00 Position 100 000 000 Alarm 2 Speed 20 00 Position 100 000 000 Hyst Speed 0 00 to 100 00 Position 100 000 000 to 100 000 000 Alarm 1 Speed 5 00 Position 1 000 Alarm 2 Speed 5 00 Position 1 000 CHANNEL BATCH SETTING...

Страница 4: ... to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Applicable wire size 0 3 0 75 mm2 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 12max 6max 3max 4min 3 2 dia mm COUNT MODE H L H Phase A H L Phase B Phase A L H Phase B L MODE 0 1 count 1 input pulse count at eit...

Страница 5: ...h 1 Alarm output 1 status 0 off 1 on Ch 1 Alarm output 2 status 0 off 1 on 1 0 2 3 0 15 Ch 2 Count direction 0 down 1 up Ch 2 Reset input status 0 open 1 short Ch 2 Alarm output 1 status 0 off 1 on Ch 2 Alarm output 2 status 0 off 1 on 5 4 6 7 Ch 1 Speed data absolute value Ch 1 Position data lower 16 bits Ch 2 Position data lower 16 bits Ch 1 Position data upper 16 bits Ch 2 Position data upper 1...

Отзывы: