INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Encoder input module .........................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

HOT SWAPPABLE MODULES

• Replacing the module does not affect other modules on 

the same base.  Thus, the module can be replaced while 
the power is ON.  However, replacing multiple modules 
at once may greatly change live voltage levels.  We highly 
recommend to replace them one by one.

 

GENERAL PRECAUTIONS

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).

ENCODER INPUT MODULE

(RS-422 input; alarm output)

MODEL

R3-PA2

Содержание R3-PA2

Страница 1: ...m ity HOT SWAPPABLE MODULES Replacing the module does not affect other modules on the same base Thus the module can be replaced while the power is ON However replacing multiple modules at once may greatly change live voltage levels We highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for main...

Страница 2: ...tions SIDE DIP SW Factory setting Input Range SW1 1 through 1 3 SW2 1 through 2 3 INPUT 1 SW1 INPUT RANGE INPUT 2 SW2 1 2 3 OFF OFF OFF 0 100 kHz ON OFF OFF 0 10 kHz OFF ON OFF 0 1 kHz ON ON OFF 0 100 Hz OFF OFF ON 0 10 Hz ON OFF ON 0 1 Hz OFF ON ON 0 0 1 Hz Count Mode SW1 4 1 5 SW2 4 2 5 INPUT 1 SW1 COUNT MODE INPUT 2 SW2 4 5 OFF OFF Mode 0 1 count pulse ON OFF Mode 1 1 count pulse OFF ON Mode 2 ...

Страница 3: ... 1 Speed High 2 Speed Low 3 Position High 4 Position Low Alarm 1 1 Speed High Alarm 2 2 Speed Low Alarm level Speed 0 00 to 100 00 Position 100 000 000 to 100 000 000 Alarm 1 Speed 80 00 Position 100 000 000 Alarm 2 Speed 20 00 Position 100 000 000 Hyst Speed 0 00 to 100 00 Position 100 000 000 to 100 000 000 Alarm 1 Speed 5 00 Position 1 000 Alarm 2 Speed 5 00 Position 1 000 CHANNEL BATCH SETTING...

Страница 4: ... to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Applicable wire size 0 3 0 75 mm2 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 12max 6max 3max 4min 3 2 dia mm COUNT MODE H L H Phase A H L Phase B Phase A L H Phase B L MODE 0 1 count 1 input pulse count at eit...

Страница 5: ...h 1 Alarm output 1 status 0 off 1 on Ch 1 Alarm output 2 status 0 off 1 on 1 0 2 3 0 15 Ch 2 Count direction 0 down 1 up Ch 2 Reset input status 0 open 1 short Ch 2 Alarm output 1 status 0 off 1 on Ch 2 Alarm output 2 status 0 off 1 on 5 4 6 7 Ch 1 Speed data absolute value Ch 1 Position data lower 16 bits Ch 2 Position data lower 16 bits Ch 1 Position data upper 16 bits Ch 2 Position data upper 1...

Отзывы: