background image

R3-NM4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8331  Rev.4  P. 6 / 8

MODBUS I/O ASSIGNMENTS

ADDRESS

DATA FORMAT NAME

Coil (0X)

1 – 1024

Digital Output (discrete output)

1025

Main / Sub Switching Command (valid only with SW3-3 set to ON)

Inputs (1X)

1 – 1024

Digital Input (discrete input)

1025 – 1040

Module Status

1041 – 1056

Error Status

1057 – 1072

Data Error Status

Input Registers (3X)

1 – 256

I

Analog Input

257 – 768

F

Analog Input

Holding Registers (4X)

1 – 256

I

Analog Output

257 – 768

F

Analog Output

I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed using floating addresses.)
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.

• Module Status indicates whether individual I/O modules are mounted or not.  The bit corresponding to the mounted slot 

turns to “1,” and the unmounted slot to “0.”

• Error Status indicates error status for each module as described below.  The bit corresponding to such module turns to “1.”

  R3-TSx, R3-RSx, R3-US4: Input burnout
  R3-DA16A: Power input in error or disconnected
  R3-YSx: Output current error (e.g. load unconnected)
  R3-PC16A: External power supply in error or disconnected

• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each 

module.  The bit corresponding to such module turns to “1.”

• Main / Sub Switching Commands given to the network modules result as follows:

‘MAIN’ MODULE

‘SUB’ MODULE

OUTPUT MODE

1

0

Main bus is used; Red light turns on at RUN LED of the I/O modules.

0

1

Sub bus is used; Green light turns on at RUN LED of the I/O modules.

1

1

Main bus is used; Amber light turns on at RUN LED of the I/O modules.

0

0

Output is invalid; RUN LED of the I/O modules turns off.

TRANSMISSION DATA ASSIGNMENTS

DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

1

     

Module 5 

 

1

     

Module 6 

 

1

     

Module 7 

 

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

ADDRESS

POSITION

Input Registers (3X)
Holding Registers (4X)

1 – 4, 257 – 264

Slot 1

Coil (0X)
Inputs (1X)

1 – 64

Slot 1

5 – 8, 265 – 272

Slot 2

65 – 128

Slot 2

9 – 12, 273 – 280

Slot 3

129 – 192

Slot 3

13, 281 – 282

Slot 4

193 – 208

Slot 4

14, 283 – 284

Slot 5

209 – 224

Slot 5

15, 285 – 286

Slot 6

225 – 240

Slot 6

16, 287 – 288

Slot 7

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned data areas (Data Allocation Type) are allotted with the Data Al-
location Type ‘1’ and ‘4.’ With ‘8’ and ‘16,’ 64 (4 × 16) are automatically allotted.

Содержание R3-NM4

Страница 1: ...tall the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperatu...

Страница 2: ...le s node address in hexadecimal with SA1 and SA2 Setpoint adjustment 01 F7 FRONT DIP SW Factory setting Baud Rate SW6 1 6 2 6 3 6 4 SW BAUD RATE bps 115 2 k 57 6 k 38 4 k 28 8 k 19 2 k 14 4 k 9600 48...

Страница 3: ...W3 2 Hold When the communication from an input module is lost due to the input module error the network module holds the signal and stands by until the communication recovers Set to 0 When the communi...

Страница 4: ...conductor terminal 1 4 2 3 6 RUN RUN RUN CONTACT OUTPUT U V POWER INPUT WIRING INSTRUCTIONS M3 SCREW TERMINAL power input RUN contact output Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing be...

Страница 5: ...13 Program Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave typ...

Страница 6: ...error or disconnected Data Error Status indicates overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresponding to such module turns to 1 Main Sub Swi...

Страница 7: ...ent 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature...

Страница 8: ...trol 1 2 3 4 5 1 When the main sub switching control for both main and sub network is set to 0 all contact outputs are off and analog output modules output 15 2 When the main s setting is switched to...

Отзывы: